Economizer oil pump screen
Figure 28: Economizer oil pump screen
This screen displays a close-up of the chiller economizer oil sump and provides all the necessary
setpoints for maintaining the Economizer Variable Speed Oil Pump (VSOP). In addition, this screen
allows manual control of the frequency command sent to the VSOP.
Table 71: Display
Field/LED
name
Access level Description
Oil Pressure
–
Displays the pressure differential between the high side oil pressure
transducer (output of oil filter) and the low side oil pressure
transducer (compressor housing). The displayed value includes
offset pressure derived from auto-zeroing during the System
Prelube (refer to explanation of auto-zeroing in
). If either of the transducers used to calculate this differential
is out of range, the display field will show XX.X.
Oil Sump
Temperature
–
Displays the temperature of the oil in the sump.
Pump Oil
Pressure
(HOP)
–
Displays the high side oil pressure measured at the compressor
bearing input.
Sump Oil
Pressure
(LOP)
–
Displays the low side oil pressure measured at the sump.
Oil Pump
Run Output
(LED)
–
Indicates whether the oil pump is operating.
YK-EP Style B Centrifugal Chiller
82
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...