Table 74: Display only
Field/LED name
Description
Leaving Chilled Liquid
Temperature
Displays the leaving chilled liquid temperature at the evaporator
and the condenser.
Delta T
Displays the temperature that is the result of the Leaving Chilled
Liquid Temperature minus the Leaving Chilled Liquid Temperature
Active Setpoint.
Control State
Displays the control state that the economizer is operating. It could
show Inactive, Cooling Control, or Motor Current, depending on the
panels Capacity Control State.
Load Limit
Displays the Active Load Limit. The following messages could be
displayed: Inactive, None, or Motor Current.
Anti-Surge Limit LED
LED is ON when the Economizer Operation Mode is Economizing
Anti Surge or Boost Anti Surge. LED is off otherwise.
Economizer Head Pressure Displays the economizer head pressure in tenths.
Active Output LED
LED on the panel lights to indicate Pre-Rotation Vanes are active.
PRV Command
Displays the position the Pre-Rotation Vanes are commanded to
open.
PRV Feedback
Displays the feedback data used to calculate the position of the Pre-
Rotation Vanes.
Control Mode
Shows what state the economizer Pre-Rotation Vane state. It may
display Manual, Auto, or Inactive, depending on what is happening
with the economizer.
Table 75: Programmable
Button
Access level Description
Manual
Increment
Service
Sets the amount the PRV position signal will Increase or Decrease
when one of those manual control buttons are pressed. (Range is
adjustable from 0.1% to 10%, Default = 10%).
Increase
Service
Pressing this button with activate the economizer Pre-Rotation
Vane override and set it to Manual, if it was previously in Auto. It
will increase the Pre-Rotation Vane override position by an amount
equal to the Manual Increment.
Auto
Service
Pressing this button will set the economizer capacity control to
Auto. This button will only be shown when the economizer capacity
control is Manual.
YK-EP Style B Centrifugal Chiller
86
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...