Economizer Solid State Starter screen
Figure 33: Economizer solid state starter screen
The Economizer Solid State Starter Screen displays information about the solid state starter used on
the economizer compressor.
Table 88: Display only
Field/LED name
Description
Motor Run LED
Indicates whether the digital output from the controls is
commanding the motor to RUN.
% Full Load Amps
Displays the motor current as a percentage of the Full Load Amps
(FLA) value.
Override Threshold
Displays the motor current upper limit as a % of FLA that the
compressor will be allowed to operate.
Input Power
Displays the kilowatts measured by the Solid State Starter.
KW Hours
Displays the cumulative amount of kilowatts used over time.
Starter Model
Displays the Solid State Starter model that is applied to the chiller.
Starter Models are 7L, 14L, 26L or 33L. This value is communicated
by the LCSSS.
Voltage (Phase A, B and C)
Displays the 3-phase input line voltage measured by the Solid State
Starter.
Current (Phase A, B and C)
Displays the 3-phase motor current values measured by the Solid
State Starter.
Temperature (Phase A, B
and C)
Displays the temperatures of the Silicon Controlled Rectifier
assemblies for each phase.
YK-EP Style B Centrifugal Chiller
96
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...