Primary compressor screen
Figure 13: Primary compressor screen
This screen displays a cutaway view of the chiller compressor, revealing the impeller, and shows all
conditions associated with the compressor. With the proper access level, the Pre-Rotation Vanes
may be manually controlled. Animation of the compressor impeller indicates whether the chiller is
presently in a RUN condition. This screen also serves as a gateway to subscreens for calibrating the
Pre-Rotation Vanes, calibrating the Proximity Probe, configuring the Hot Gas Bypass, or providing
advanced control of the Compressor Motor Variable Speed Drive.
Note:
For fields requiring access level of SERVICE. Qualified service technicians should refer
to the OptiView Control Center Service for operation instructions and explanations of all
programmable setpoints and displayed values.
Table 26: Display only fields
Field/LED
name
Access level Description
Oil Sump
Temperature
–
Displays the temperature of the oil in the sump
Discharge
Temperature
–
Displays the temperature of the refrigerant in its gaseous state at
discharge of the compressor as it travels to the condenser.
Discharge
Superheat
–
Displays the discharge superheat, calculated as Discharge
Temperature – Condenser Saturation temperature.
High Speed
Thrust
Bearing
Proximity
Differential
–
Displays the present position of the High Speed Thrust Bearing in
relation to neutral. Locations are shown in mils. Zero indicates that
the bearing is in the normal position.
YK-EP Style B Centrifugal Chiller
42
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...