Economizer compressor Variable Geometry Diffuser screen
Figure 23: Economizer compressor VGD screen
This screen displays information pertinent to the Economizer VGD operation. Also, the Economizer
VGD can be manually controlled from this screen.
Table 56: Display only
Field/LED name
Description
Stall Detector Voltage
Displays the Stall Detector output voltage as received by the
Microboard.
High Limit
Displays the voltage, that if exceeded, will result in the VGD closing
to prevent a stall from occurring.
Low Limit
Displays the voltage, that if has dropped below the setpoint, will
cause the VGD to open, allowing more gas through the compressor.
Mach Number
Displays the speed of the refrigerant gas leaving the compressor in
percentage of Mach (the speed of sound).
VGD Closed Limit Switch
Displays the status of the VGD Limit Switch. Displayed as CLOSED
when the switch is closed. This would be when the VGD is in the fully
closed position. Otherwise, displayed as OPEN.
VGD Opening (LED)
Illuminates when a close signal is being applied to the VGD.
VGD Closing (LED)
Illuminates when an open signal is being applied to the VGD.
Stall Count
Displays the number of times that the system had detected an
Economizer Compressor Stall.
Stall Time
Displays the accumulated time that the Stall Detector Board output
is greater than the High Limit Setpoint voltage while the chiller is
running.
69
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...