Table 114: Programmable
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Select Run/Stop Operator
Standard
Allows the user to select the Control Source for Run/Stop (Local, BAS or
Hardwire).
Select Cooling Operator
Standard
Allows the user to select the Control Source for Cooling. (Local, BAS, 0 VDC
to 10 VDC, 4 mA to 20 mA, or PWM) and also set the remote analog signal
minimum and maximum value setpoints. The remote analog signal can
adjust the setpoint between the user selected Maximum (max signal) and
the user selected Minimum (min signal). Refer to
Form 160.76-PW4
for
more details on the BAS interfaces.
Select Current
Limit
Operator
Standard
Allows the user to select the Control Source for Current Limiting. (Local,
BAS, 0 VDC to 10 VDC, 4 mA to 20 mA, or PWM). The remote analog signal
can adjust the setpoint between 30% (max signal) and 100% (min signal).
Refer to
Form 160.76-PW4
for more details on the BAS interfaces.
Table 115: Navigation
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Home
View
View
Returns the user to Home screen.
Setpoints
View
View
Navigates to the Setpoints Screen.
Operations
View
View
Navigates to the Operations Screen.
117
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center