System screen
Figure 26: System screen
This screen gives a general overview of common chiller parameters for both shells.
Table 10: Display only fields
Field/LED name
Description
Discharge Temperature
Displays the temperature of the refrigerant in its gaseous state at discharge of the
compressor as it travels to the condenser.
Motor % Full Load Amps
This displays the percentage of Full Load Amps utilized by the system.
Current Limit Setpoint
Displays the current limit value in use. This value could come from a 4 mA to 20 mA, 0
VDC to 10 VDC, PWM signal, SC-EQ interface BAS mode, or a locally programmed value.
Condenser Liquid Temperature –
Entering
Displays the temperature of the liquid as it enters the condenser.
Condenser Liquid Temperature –
Leaving
Displays the temperature of the liquid as it leaves the condenser.
Condenser Liquid Temperature –
Setpoint
Displays the active setpoint to which the Heat Pump is controlling the Leaving
Condenser Liquid Temperature. Only displayed when Heat Pump is enabled on the
SETUP Screen and the Operation mode is set to Heating mode on the HEAT PUMP
Screen. The setpoint could come from a 4 mA to 20 mA, 0 VDC to 10 VDC, PWM, or SC-
EQ interface in BAS mode, or a locally programmed value.
Head Pressure
Displays the pressure difference between the condenser and evaporator (condenser
minus evaporator). This is also called the Head Pressure. This is only displayed when
Head Pressure Control is enabled.
Head Pressure Setpoint
Displays the active Head Pressure Setpoint to which the head pressure is being
controlled. This is only displayed when Head Pressure Control is enabled.
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Condenser Saturation
Displays the saturation temperature in the condenser.
Oil Sump Temperature
Displays the temperature of the oil in the sump. (Only displayed when a Variable
Speed Oil Pump is installed.)
31
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center