Condenser screen
Figure 28: Condenser screen
This screen displays a cutaway view of the chiller condenser. All setpoints relating to the condenser
side of the chiller are maintained on this screen. Animation indicates condenser liquid flow. When
Heat Recovery is enabled, the condenser flow animation will show flow when either the Condenser
Liquid Flow Switch or the Heating Condenser Liquid Flow Switch says flow is present. When Heat
Recovery is disabled, the condenser flow animation is based on the standard Condenser Flow
Switch. This screen also serves as a gateway to controlling the Refrigerant Level, Heat Recovery, and
Head Pressure Control.
Table 15: Display only fields
Field/LED name
Description
Leaving Condenser Liquid
Temperature
Displays the liquid temperature as it leaves the condenser.
Leaving Condenser Liquid
Temperature Setpoint
Displays the active setpoint to which the Heat Pump is controlling the Leaving
Condenser Liquid Temperature. Only displayed when Heat Pump is enabled on the
SETUP Screen and the Operation mode is set to Heating mode on the HEAT PUMP
Screen.
Entering Condenser Liquid
Temperature
Displays the water temperature as it enters the condenser.
Condenser Saturation Temperature Displays the saturation temperature in the condenser.
Condenser Small Temperature
Difference
Displays the difference between the Condenser Refrigerant temperature and the
Leaving Condenser Liquid temperature. The Condenser Refrigerant temperature will
be represented by the Condenser Saturation temperature.
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Leaving Heating Condenser Liquid
Temperature
Displays the temperature of the liquid as it leaves the heating condenser tube bundle.
Appears when the Heat Recovery is enabled.
Entering Heating Condenser Liquid
Temperature
Displays the temperature of the liquid as it enters the heating condenser tube bundle.
Appears when the Heat Recovery is enabled.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center