background image

FORM 160.52-M2

YORK INTERNATIONAL

11

STATUS LED

00132VIP

OIL PUMP DRIVE STATUS LED

The VSOP drive has a drive status LED located in the
lower right corner on the control board near the mount-
ing screw. The panel door for the VSOP drive must be
opened to view the drive status LED. The state and
color of the LED can determine the status of the VSOP
drive. The condition of the LED is as follows:

• A constant GREEN LED will indicate that the

VSOP drive is in a running condition with no fault
conditions valid.

• A constant RED LED will indicate that the VSOP

drive is in a stopped condition, or torque limit during
a running condition.

• If the LED is not lit at all, the VSOP drive has failed

or the input power has been removed.

• A flashing RED LED will indicate that the VSOP

drive is in a faulted condition. The fault conditions
are explained below.

VSOP DRIVE OKAY RELAY

The VSOP drive is equipped with a set of normally open
contacts. These contacts are open when the VSOP drive
is in a faulted condition. These contacts are driven
closed when the VSOP drive condition is okay. The
contacts are connected between TB1-70 and TB1-1.
When the contacts are open a voltage of 115VAC will
be measured at the TB1 connections and the chiller will
initiate a Cycling Shutdown. The following message will
appear on the display when the STATUS key is pressed
on the Microcomputer Control Center.

FAULT INDICATIONS FROM THE VSOP DRIVE

    DAY-TIME-OIL PUMP DRIVE - AUTOSTART

Refer to the fault conditions below to determine if the
Cycling Shutdown will auto reset. If the shutdown is of
the type that will auto reset, the drive okay relay will
close the contacts when the fault has cleared. If the
shutdown is not of the type that will auto reset, the drive
okay relay will not close the contacts unless the input
power to the VSOP drive is removed for 30 seconds
and reapplied.

AUTO RE-SETTABLE SHUTDOWNS

When the VSOP drive okay relay de-energizes one of
the following faults has occurred.

Heatsink Overtemperature

The temperature of the VSOP drive heatsink has ex-
ceeded 100ºC. The VSOP drive will restart automati-
cally when the heatsink temperature is less than 100ºC.

Possible Problems:
The drive is located in a location that is too hot. The
mechanical room may be too hot, or the location of
the VSOP drive may be too close to the discharge of
the compressor.
Possible Soultions:
Locate the VSOP drive in a cooler location. Move
the VSOP drive away for the discharge of the com-
pressor.

Undervoltage

• A 230 volt unit will fault if the input voltage falls

below 140VAC for a period of time greater than 40
seconds or instantly if the input voltage is less than
139VAC.

• A 460 volt unit will fault if the input voltage falls

below 280VAC for a period of time greater than 40
seconds or instantly if the input voltage is less than
279VAC.

A 460 volt unit with a 575VAC line and a trans-
former will fault if the input voltage falls below
350VAC for a period of time greater than 40 sec-
onds or instantly if the input voltage is less than
349VAC.

The VSOP drive will restart automatically 10 seconds
after the fault has cleared.

Possible Problems:
There may be noise on the input line, or the line volt-
age may not be correct.
Possible Solutions:
Verify the input voltage.

Summary of Contents for YK

Page 1: ...MODEL YK MODEL D E CENTRIFUGAL LIQUID CHILLERS SERVICE INSTRUCTIONS VARIABLE SPEED OIL PUMP DRIVE Supersedes Nothing Form 160 52 M2 899 00130VIP...

Page 2: ...SOP DRIVE 11 Oil Pump Drive Status LED 11 VSOP Drive Okay Relay 11 Auto Resettable Shutdowns 11 Non Auto Resettable Shutdowns 12 TROUBLESHOOTING GUIDE 13 DRIVE REPLACEMENT INSTRUCTIONS 14 MOST FREQUEN...

Page 3: ...r the standard chiller Version C 02T 16 Part Number 031 01431 003 will be avail able for Remote Chiller Communications applications The Micro Board will change from a 031 01065 001 to a 031 01065 002...

Page 4: ...Z PRS XX XPSID MICROCOMPUTER CONTROL CENTER OPERATION The Microcomputer Control Center maintains desired system oil pressure by controlling the speed of the oil pump The speed at which the oil pump ru...

Page 5: ...LOSE REFRIGERANT LEVEL OPEN OIL PUMP VSD SPEED CONTROL 3R 1M 2 1 HTR J10 1 2 3 J2 2 J2 1 J2 3 REFRIGERANT LEVEL CONTROL BOARD OIL PUMP VARIABLE SPEED DRIVE PWM RUN V 3R 1 J4 2 J4 1 J3 2 J5 1 J1 2 12 V...

Page 6: ...ultiples of 0 3 seconds over the range of 0 3 to 2 7 seconds by programming a MULTIPLIER value of 1 through 9 The program multiplies this value by 0 3 to produce pe riods over the range of 0 3 to 2 7...

Page 7: ...PUMP VARIABLE SPEED DRIVE LD04377 12 VDC 0VDC OFF TIME ON TIME OFF ON 12 VDC 0 VDC 12 VDC 0 VDC OFF ON OFF ON OFF ON OFF ON 0 7 SEC 0 52 SEC 0 35 SEC 0 17 SEC 25 0 Hz 33 5 Hz 42 5 Hz 51 0 Hz 60 0 Hz O...

Page 8: ...oil pump speed control perform the following 1 This procedure assumes VSOP drive operation has been selected using the procedure below under Programming 2 Using Access Code 1 3 8 0 enter Program Mode...

Page 9: ...01065 002isrequiredonallVSOPdriveapplications STANDBY LUBRICATION To maintain oil seal integrity while the chiller is shut down the oil pump is turned on for 2 minutes every 24 hours if the chiller ha...

Page 10: ...5 minute SYSTEM COASTDOWN op SAFETY SHUTDOWNS eration is performed when power is restored During the SYSTEM COASTDOWN the oil pump runs If configured for AUTO RESTART AFTER POWER FAILURE a SYSTEM COAS...

Page 11: ...tdown will auto reset If the shutdown is of the type that will auto reset the drive okay relay will close the contacts when the fault has cleared If the shutdown is not of the type that will auto rese...

Page 12: ...the cur rent is increased at 4 3 amps a shutdown will occur in 40 seconds The VSOP drive will restart when input power is re moved for 30 seconds and reapplied Possible Problems Something maybe bindin...

Page 13: ...on the 1 Measure voltage between 1 a If 0 VAC is measured Microcomputer Control Center terminal 1on the VSOP drive replace VSOP drive reads OIL PUMP DRIVE and Ground 1 b If 115 VAC is measured AUTOST...

Page 14: ...1 Refer to the second paragraph autostart everyday at the same time under Known Problems on Page 3 The oil pump motor rotation 1 Reverse two of the wires on is reverse M1 M3 of the VSOP drive DRIVE R...

Page 15: ...FORM 160 52 M2 YORK INTERNATIONAL 15 LD04378 OR FIG 3 SYSTEM WIRING DIAGRAM...

Page 16: ...ng start up by gradually turn ing on SCR s connected to the input line Inrush current is reduced since the voltage applied to the motor is reduced This method of controlling a motor has no effect on t...

Page 17: ...ore Part Center with the following part number WAEXRK01 Yes this is a real YORK part number and the last two digits are zero one Operation of the RKU is covered in Form 160 00 NO7 VSOP DRIVE 230 VAC U...

Page 18: ...drive used in the Mod E YK chiller is the same as the VSOP drive used in the Mod D YK chiller described on pages 3 thru 17 Refer to pages 3 thru 17 for detailed information about fault messages and t...

Page 19: ...t of normally open contacts These contacts are open when the VSOP drive is in a faulted condition These contacts are driven closed when the VSOP drive condition is okay The contacts are connected betw...

Page 20: ...ashing RED on the VSOP drive Status display on the 1 Measure voltage between 1 a If 0 VAC is measured Microcomputer Control Center terminal 1 on the VSOP drive replace VSOP drive reads OIL PUMP DRIVE...

Page 21: ...hould run at 60 Hz If the oil pressure does not increase replace the VSOP drive 3 Remove the wire from J20 1 on the micro board Connect a 10K resistor to J20 1 and 12V supply Program the oil pump for...

Page 22: ...3 SPEED COMMAND START STOP 12VDC MICRO BOARD J19 J20 6 PWM V EN OIL PUMP VSD I O BOARD TB3 J1 6 70 TB3 1 70 1 OIL VARIABLE SPEED PUMP DRIVE CONTACTS OPEN LINE DRIVE OKAY RELAY OPEN ON FAULT FIG 4 OIL...

Page 23: ...FORM 160 52 M2 YORK INTERNATIONAL 23...

Page 24: ...P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1999 ALL RIGHTS RESERVED Form 160 52 M2 899 Supersedes Nothing...

Reviews: