background image

JOHNSON CONTROLS

7

FORM 160.75-N3 

ISSUE DATE: 04/15/2019

1

INTRODUCTION

This instruction explains the procedure to be used for 

reassembling the Model YK Chiller shipped disassem-

bled (Shipping Form 3 and 7).

Chillers MUST be field reassembled un

-

der the supervision of a Johnson Controls 

representative.

For instructions on installing the unit, refer to the 

In-

stallation - Unit (Form 160.75-N1)

.

FORMS OF SHIPMENT

Form 3 – Driveline Separate From Shells – 

Shipped 

as two major assemblies. The unit is first factory as-

sembled, refrigerant piped, wired and leak tested; then 

dismantled for shipment. Close-coupled compressor/

open motor assembly is removed from shells and skid-

ded; however, the evaporator/condenser is not skidded.

All wiring integral with compressor is left on it, and all 

conduit is left on the shell. All openings on the com-

pressor and shell are closed and charged with dry ni-

trogen (2 to 3 PSIG).
The shipment may include miscellaneous packaging of the 

control center, oil eductor filter, tubing, water temperature 

controls, wiring, oil, isolators, solid state starter or variable 

speed drive (options). The refrigerant charge is shipped in 

appropriate cylinders. For P and Q compressors the control 

panel is removed for shipment. For H9 and K compressors 

the control panel is shipped on a folded bracket. Refer to 

the 

Installation - Unit (Form 160.75-N1)

 for more details.

Form 7 – Split Shells – 

Shipped as three major assem-

blies. The unit is first factory assembled, refrigerant 

piped, wired and leak tested; then dismantled for ship-

ment. Close-coupled compressor/open motor assembly 

is removed from shells and skidded.
The evaporator and condenser shells are separated at 

tube sheets and are not skidded. The refrigerant lines 

between the shells are flanged and capped; tube sheets 

are also bolted, requiring NO welding.

LD15222

CONDENSER

CONTROL

CENTER

COMPRESSOR

MOTOR

EVAPORATOR

FIGURE 1 - 

FRONT VIEW OF ASSEMBLED UNIT

SECTION 1 - SHIPPING AND REASSEMBLY

Summary of Contents for YK

Page 1: ...ERS STYLE G R 134a OR R 513A COOLING ONLY WITH GRAPHIC CONTROL CENTER FOR ELECTROMECHANICAL STARTER SOLID STATE STARTER AND VARIABLE SPEED DRIVE CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS S...

Page 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Page 3: ...unted MV SSS Manufactured Before 2007 160 00 O5 Operation Floor Mounted MV SSS Manufactured After 2007 160 00 O5 1 Operation Unit Mounted MV SSS 160 00 O7 Operation MV VSD 2300 VAC 6600 VAC 160 00 O6...

Page 4: ...04 15 2019 NOMENCLATURE YK KC K4 H9 CY G MOTOR CODE POWER SUPPLY for 60 Hz 5 for 50 Hz COMPRESSOR CODE CONDENSER CODE EVAPORATOR CODE MODEL STYLE Design Level Refer to YK Engineering Guide Form 160 75...

Page 5: ...amage Shortage 8 Data Plates 9 Long Term Storage 9 Reassembly 11 Q3 Q7 and P7 Compressors Without Falling Film 14 Q3 Q7 and P7 Compressors with Falling Film 16 Q3 Q7 and P7 Compressors System Piping 1...

Page 6: ...3 Q7 And P7 Compressors With Falling Film 16 FIGURE 9 Form 7 Shipment Q3 Q7 And P7 Compressors With Falling Film 17 FIGURE 10 System Piping Q3 Q7 And P7 Compressors 18 FIGURE 11 Form 3 Shipment K Comp...

Page 7: ...with dry ni trogen 2 to 3 PSIG The shipment may include miscellaneous packaging of the control center oil eductor filter tubing water temperature controls wiring oil isolators solid state starter or v...

Page 8: ...2 psig to 3 psig Miscellaneous packaging of tubing water temperature controls wiring isolators etc The unit is shipped with a nitrogen charge The refrigerant charge is shipped in appropriate cylinder...

Page 9: ...f material under pres sure and to protect themselves 1 Check that the working space is open and has good ventilation If is does not have good ventila tion connect a hose or pipe to the valve Item 5 an...

Page 10: ...5 6 7 Nozzle without flanges Lines 4 in through 12 in Nozzle without flanges Lines 14 in through 24 in 8 9 8 9 ITEM DESCRIPTION 1 Tag Warning Dennison 8E 2 Gauge Press 2 Dia 0 30 3 Tag GlvSt Wire Spee...

Page 11: ...onnection Check the transverse alignment by placing a level on the tops of both end sheets Refer to the Installation Unit Form 160 75 N1 for additional instructions to level the unit After shell is le...

Page 12: ...placing a level on the tops of both end sheets refer to Installation Unit Form 160 75 N1 for additional instructions to level the unit After shell is leveled wedge and shim each corner of the shell t...

Page 13: ...unted MV SSS Form 160 75 PW2 7 Reconnect all unit wiring and harnesses refer to Wiring Diagrams Field Connections Remote Mounted MV SSS Form 160 75 PW2 8 Pressure test the unit Relief valves must be p...

Page 14: ...Q7 AND P7 COMPRESSORS WITHOUT FALLING FILM LD13170 SUCTION LINE DISCHARGE LINE DISCHARGE ISOLATION VALVE IF FURNISHED HOT GAS VALVE IF FURNISHED RING GASKETS See NOTE CONDENSER EVAPORATOR Q3 Q7 AND P...

Page 15: ...Q3 Q7 AND P7 COMPRESSORS WITHOUT FALLING FILM CONDENSER EVAPORATOR SUCTION LINE ISOLATION VALVE IF FURNISHED HOT GAS VALVE IF FURNISHED LIQUID LINE VALVE IF FURNISHED RING GASKETS See NOTE Q3 Q7 AND...

Page 16: ...ON VALVE IF FURNISHED HOT GAS VALVE IF FURNISHED RING GASKETS See NOTE CONDENSER EVAPORATOR LD13171b CONDENSER EVAPORATOR LIQUID LINE LD13170a Figure 8 FORM 3 SHIPMENT Q3 Q7 AND P7 COMPRESSORS WITH FA...

Page 17: ...NISHED HOT GAS VALVE IF FURNISHED RING GASKETS See NOTE CONDENSER EVAPORATOR LD13171b Figure 9 FORM 7 SHIPMENT Q3 Q7 AND P7 COMPRESSORS WITH FALLING FILM Q3 Q7 AND P7 COMPRESSORS CONT D WITH FALLING F...

Page 18: ...19 Section 1 Shipping and Reassembly LD13174 Figure 10 SYSTEM PIPING Q3 Q7 AND P7 COMPRESSORS Q3 Q7 AND P7 COMPRESSORS SYSTEM PIPING SUCTION LINE 3 8 OIL RETURN LINE 3 8 OIL RETURN LINE 3 8 COMPRESSOR...

Page 19: ...FORM 3 SHIPMENT K COMPRESSORS LD13172 Ring Gaskets See NOTE DISCHARGE SPOOL ISOLATION VALVE IF FURNISHED SUCTION LINE HOT GAS VALVE IF FURNISHED OIL LINE OIL PUMP PANEL CONTROL PANEL CONDENSER EVAPOR...

Page 20: ...gure 12 FORM 7 SHIPMENT K COMPRESSORS LD13173 CONDENSER EVAPORATOR HOT GAS IF FURNISHED LIQUID LINE OIL LINE RING GASKETS See NOTE DISCHARGE SPOOL SUCTION LINE ISOLATION VALVE IF FURNISHED K COMPRESSO...

Page 21: ...ng and Reassembly FORM 160 75 N3 ISSUE DATE 04 15 2019 1 LD13175 Figure 13 SYSTEM PIPING K COMPRESSORS K COMPRESSORS CONT D 3 4 OIL SUPPLY LINE 1 OIL SUMP VENT LINE 3 8 LIQUID INJECTION LINE 1 REFRIGE...

Page 22: ...P9 AND H9 COMPRESSORS WITHOUT FALLING FILM SUCTION LINE DISCHARGE SPOOL ISOLATION VALVE IF FURNISHED HOT GAS VALVE IF FURNISHED OIL PUMP PANEL CONTROL PANEL CONDENSER EVAPORATOR RING GASKETS See NOTE...

Page 23: ...WITHOUT FALLING FILM SUCTION LINE DISCHARGE SPOOL DISCHARGE ISOLATION VALVE IF FURNISHED HOT GAS VALVE IF FURNISHED LIQUID LINE VALVE CONTROL PANEL OIL PUMP CONTROL PANEL RING GASKETS See NOTE CONDEN...

Page 24: ...M P8 P9 AND H9 COMPRESSORS WITH FALLING FILM FROM CONDENSER TO EVAPORATOR LIQUID LINE LIQUID LINE FROM CONDENSER TO EVAPORATOR DISCHARGE SPOOL SUCTION LINE ISOLATION VALVE IF FURNISHED HOT GAS VALVE I...

Page 25: ...ATOR SUCTION LINE DISCHARGE SPOOL DISCHARGE ISOLATION VALVE IF FURNISHED HOT GAS VALVE IF FURNISHED CONTROL PANEL OIL PUMP CONTROL PANEL RING GASKETS See NOTE LD13185b Figure 17 FORM 7 SHIPMENT P8 P9...

Page 26: ...9 Section 1 Shipping and Reassembly P8 P9 AND H9 CCOMPRESSORS SYSTEM PIPING SUCTION LINE 3 8 OIL RETURN LINE 3 8 OIL RETURN LINE 3 8 COMPRESSOR TO VSOP PANEL 3 4 OIL RETURN LINE 3 4 OIL SUPPLY LINE Fi...

Page 27: ...elsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 1 SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons Refrigerant Effe...

Page 28: ...Pennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2019 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 75 N3 419 Issue Date Apri...

Reviews: