JOHNSON CONTROLS
FORM 160.75-EG1 (519)
64
Application Data (Cont'd)
NOTES:
1.
For motor starters above 4160V/60Hz and 3300/50Hz, contact the Johnson Controls Sales Office for a specific selection.
2. Minimum tap for 5DJ motor is 80%.
TABLE 13 -
MOTOR STARTERS
TYPE
STARTER
SOLID-
STATE
STARTER
STAR
DELTA
AUTO TRANSFORMER
ACROSS-
THE-LINE
PRIMARY REACTOR
VOLTAGE
LOW/
MEDIUM
LOW
LOW
LOW/
MEDIUM
LOW/
MEDIUM
LOW/
MEDIUM
MEDIUM
MEDIUM
60 HZ
200-4160
200-600
200-600
200-4160
200-4160
200-4160
2300-4160
2300-4160
50 HZ
380-3300
346-415
346-415
346-3300
346-3300
346-3300
2300-3300
2300-3300
TRANSITION
% TAP INRUSH
AS A %
OF LRA
—
CLOSED
CLOSED
CLOSED
CLOSED
—
CLOSED
CLOSED
—
—
57.7
65
80
—
65
80
45
33
33
42.3
64
100
65
80