FORM 160.75-EG1 (519)
JOHNSON CONTROLS
69
Application Data (Cont'd)
TABLE 17 -
MEDIUM VOLTAGE UNIT MOUNTED SOLID-STATE STARTER MODELS
UNIT MOUNTED
MV-SSS
MAXIMUM
FLA
MAXIMUM
LRA
RATED
VOLTAGE &
FREQUENCY
UMVSSS0853K105-V V
105
1896
2300/60HZ
3300/50Hz
4160/60HZ
UMVSSS0853K190-V V
190
1896
UMVSSS0853K280-V V
280
1896
UMVSSS0853K389-V V
389
1896
UMVSSS1708K389-V V
389
3796
MEDIUM VOLTAGE UNIT MOUNTED
SOLID STATE STARTER NOMENCLATURE
UMVSSS 0853 K 105 - 80
VOLTAGE CODE
80 = 2300V/60Hz
92 = 3300V/50Hz
94 = 4180V/60Hz
K = YK OIL PUMP SUPPLY
MAXIMUM JOB
FLA CURRENT
105 = 105 AMPS
190 = 190 AMPS
280 = 280 AMPS
389 = 389 AMPS
MAXIMUM
STARTING CURRENT
0853 - 853 AMPS
1708 - 1708 AMPS
LD19168