FORM 160.75-EG1 (519)
JOHNSON CONTROLS
93
MARINE WATER BOXES - 150 PSI ROUND
CONDENSER
SHELL CODE
NOZZLE PIPE
SIZE(IN)
1-PASS
2-PASS
3-PASS
NO. OF PASSES
1
2
3
D
S
5
S
5
T
5
U
S
5
T
5
U
A
10
6
6
1' 3"
(381)
3' 11"
(1194)
3' 11"
(1194)
1' 8"
(508)
1' 3-3/8"
(391)
3' 11"
(1194)
1' 8"
(508)
1' 3-3/8"
(391)
C,D
12
8
6
1' 3-1/2"
(394)
4' 3"
(1295)
4' 3"
(1295)
1' 8"
(508)
1' 6-1/2"
(470)
4' 3"
(1295)
1' 8"
(508)
1' 6-1/2"
(470)
E,F
14
10
8
1' 5-1/2"
(445)
4' 7"
(1397)
4' 7"
(1397)
1' 10"
(559)
1' 9"
(533)
4' 7"
(1397)
1' 10"
(559)
1' 9"
(533)
J,K,L
16
10
10
1' 8"
(508)
5' 1"
(1549)
5' 1"
(1549)
1' 9"
(533)
1' 9-1/2"
(546)
5' 1"
(1549)
1' 9"
(533)
1' 9-1/2"
(546)
M,N
20
14
10
1' 11"
(584)
5' 9-7/8"
(1775)
5' 9-7/8"
(1775)
2' 4"
(711)
2' 1-1/2"
(648)
5' 9-7/8"
(1775)
2' 4"
(711)
2' 1-1/2"
(648)
P,Q
20
16
14
2' 1-1/4"
(641)
6' 2-3/8"
(1889)
6' 2-3/8"
(1889)
2' 4-1/2"
(724)
2' 5-1/2"
(749)
6' 2-3/8"
(1889)
2' 4-1/2"
(724)
2' 5-1/2"
(749)
R,S
20
18
14
2' 3-1/2"
(699)
6' 7"
(2007)
6' 7"
(2007)
2' 6-1/2"
(775)
2' 8-1/2"
(826)
6' 7"
(2007)
2' 6-1/2"
(775)
2' 8-1/2"
(826)
T,V,W
24
18
16
2' 5-1/2"
(749)
6' 10-1/4"
(2089)
6' 10-1/4"
(2089)
2' 6"
(762)
2' 10"
(864)
6' 10-1/4"
(2089)
2' 6"
(762)
2' 10"
(864)
X,Z
24
20
16
2' 8"
(813)
7' 2"
(2184)
7' 2"
(2184)
2' 7-3/4"
(806)
2' 11-1/2"
(902)
7' 2"
(2184)
2' 7-3/4"
(806)
2' 11-1/2"
(902)
NOTES:
1. All dimensions are ft-inches (mm).
2. Standard water nozzles are furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option of welding, flanges, or
use of ANSI/AWWA C-606 couplings. Factory-installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6 mm raised
face), water flanges nozzles are optional (add 13 mm to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished.
3. One, two and three pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporator nozzles may
be used in combination with any pair of condenser nozzles.
4. Evaporator and condenser water must enter the water box through the bottom connection to achieve rated performance.
5. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
6. Add dimension "M" as shown on
for the appropriate isolator type.
7. Standard 150 psi (1034 kPa) design pressure water boxes shown.
8. Shell codes R, S, T, V, W, X, and Z use double letter nozzle codes in the same orientation as the single letter e.g. P = PP.
CONDENSERS – MARINE WATERBOXES
Dimensions (Cont'd)
Summary of Contents for YK
Page 4: ...JOHNSON CONTROLS FORM 160 75 EG1 519 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...JOHNSON CONTROLS FORM 160 75 EG1 519 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 59 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 83: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 83 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 91 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 113 THIS PAGE INTENTIONALLY LEFT BLANK...