background image

JOHNSON CONTROLS

12

Form 160.00-N6  

Issue date: 08/27/2021

Section 1 - Field connection notes

13.  The YORK MVVSD input power wiring ampac-

ity is calculated as follows:
Model YK, YD, and YK-EP minimum circuit am-

pacity for each starter:

Ampacity = 1.25X (Compressor Motor FLA) 

+ Oil Pump Drive Panel Amps + Control 

Power Transformer Amps

Where:

•  125% factor is outlined in 2005 NEC (

Para-

graph 440-33

• 

FLA is as outlined in product specific infor

-

mation, for example, the performance report 

or sales report that has the job specific condi-

tions.

•  The oil pump panel and control transform-

er amps are as shown in 

Table 2

. Oil pump 

panel and control transformer amps value 

used, to be adjusted by ratio of (120/[MV-

VSD nameplate voltage]). Oil pump amps 

to be included if MVVSD optional oil pump 

power supply is included. 

14.  Medium voltage (2.3 KV to 6.6 KV) motors have 

three leads. Motor leads are supplied with a crimp 

type connector having a clearance hole for a 3/8 in. 

bolt. Motor terminal lugs are not supplied.

15.  Starter to motor power wiring ampacity is calcu-

lated as follows:
Minimum circuit ampacity for each conductor 

(one of three): 

Ampacity = 1.25 x compressor motor amps 

Where: 

•  125% factor is outlined in 2005 NEC (

Para-

graph 440-33

)

• 

Compressor motor amps are FLA. See product-

specific information, for example, the perfor-

mance report or sales report that has the job 

specific conditions.

16. 

The condenser flow switch is optional. If not pres

-

ent, a jumper must be installed between TB4-11 

and TB4-1.

17.  The interrupting capacity of the YORK MVVSD 

is 50 KA RMS symmetrical amperes at the name-

plate voltage. The YORK MVVSD is suitable for 

use on a circuit capable of delivering not more 

than 50 KA RMS symmetrical amperes at the 

nameplate voltage.  

18.  Three-phase oil pump motor must be correctly 

phased. L1, L2, and L3 correspond to phase se

-

quence A, B, and C.

19.  Control circuit wiring for 3M condenser wa-

ter pump motor starter is shown for cooling 

only application. For units with Flash Miniature 

Card  Software  Version  C.MLM.01.00  through 

C.MLM.01.03,  the  condenser  water  pump  must 

be wired to Terminal 164 of TB2 instead of Ter-

minal 151. The wire from Terminal 22 of TB5 to 

Terminal 150 of TB2 must not be installed. 

20.  The main power transformer must be adequately 

sized such that the transformer voltage drop does 

not exceed 10% and 15% during unit start-up. The 

supply voltage, at starter input terminals, during 

start-up must be maintained above the minimum 

value  specified  in  the  following  table.  Note  that 

while the YORK chiller performs acceptably dur-

ing startup with this amount of voltage drop, the 

performance of other equipment connected to the 

supply transformer could be adversely affected.

Table 3 - 

Minimum voltage during start-up

Three-phase 

voltage

Hz

Minimum voltage at  

drive input terminals  

during start-up

2,300

50

1,955 V

3,300

50/60

2,805 V

4,160

60

3,536 V

6,600

60

5,610 V

21.  Automatic control of the chilled water pump by the 

OptiView Control Center is shown. Chilled wa-

ter pump motor starter (5M) holding coil must be 

equipped for 115 V, 50 Hz or 60 Hz. The power re-

quirements for the water pump starter (5M) must be 

a maximum of 1 A holding and 8 A inrush. If power 

requirements exceed this value, equip the coil for 

line voltage, and the control relay with 115 V coil.
The pumps operate during oil pump pre-run, dur-

ing compressor operation, and during cycling 

shutdown.

22. 

Each 115 VAC field-connected inductive load, that is 

relay coil, motor starter coil, and others, must have a 

transient suppressor wired by others in parallel with 

its coil, physically located at the coil. Spare transient 

suppressors are factory supplied in a bag attached to 

the keypad cable clamp in the Control Center.

23.  Unit dimensions, weights, incoming cable locations, 

and exhaust details are provided by YORKworks.

Summary of Contents for YK

Page 1: ...stallation Supersedes 160 00 N6 919 Form 160 00 N6 821 Medium Voltage 500 hp to 2500 hp 2300 V 3300 V 4160 V and 6600 V 60 Hz 3300 V and 6600 V 50 Hz Variable Speed Drives for YK YD and YK EP Chiller...

Page 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Page 3: ...ge to Dissipate To A Safe Level Before Working On Equipment Only Qualified Personnel Should Be Permitted To Operate Or Service This Equipment Disconnect And Lock Out Primary And Control Circuit Power...

Page 4: ...lers It is the responsibility of rigging lifting and operating service personnel to verify the applicability of these documents to the equipment If there is any question regarding the applicability of...

Page 5: ...approval cUL UL and CE Environmental 32 F to 104 F 0 C to 40 C max 95 humidity non condensing 5000 ft 1524 m altitude Vibration 0 5 G or less at 10 Hz to 60 Hz Enclosure NEMA 1 IP20 IEC 529 MVVSD req...

Page 6: ...21 Handling and storage 21 Location 22 Drive lifting and assembly 22 Mounting requirements 23 Mounting 23 Electrical connection 24 Control wiring 24 Power wiring 24 Grounding 25 Oil pump wiring 26 Up...

Page 7: ...GURE 10 Ground bus splice connection 25 FIGURE 11 Oil pump connections 26 TABLE 1 Unit model reference 8 TABLE 2 Oil pump drive power supply 11 TABLE 3 Minimum voltage during start up 12 TABLE 4 Contr...

Page 8: ...0 lb 2 722 kg MVVSD2250RK 80 2300 60 2300 60 2250 494 12 500 lb 5 670 kg 6 000 lb 2 722 kg 222 x 50 x 104 564 x 127 x 264 MVVSD2500RK 80 2300 60 2300 60 2500 561 12 500 lb 5 670 kg MVVSD0500RK 92 3300...

Page 9: ...000 lb 5 443 kgs MVVSD2250RK 94 3300 60 3300 60 2250 345 12 700 lb 5 761 kgs 5 500 lb 2 495 kg 174 x 50 x 104 442 x 127 x 264 MVVSD2500RK 94 3300 60 3300 60 2500 391 13 500 lb 6 123 kgs MVVSD0500RK 8...

Page 10: ...60 2250 274 11 200 lb 5 080 kg 4 500 lb 2 041 kg 164 x 50 x 104 417 x 127 x 264 MVVSD2500RK 95 6600 50 4160 60 2500 310 12 000 lb 5 443 kg MVVSD0500RK 85 6600 60 4160 60 500 62 6 400 lb 2 903 kg 74 x...

Page 11: ...voltage and thecontrol relay with 115 V coil 9 Wire 14AWG copper for one way distance of less than 175 ft Wire 12AWG copper for one way dis tance of more than 175 ft but less than 300 ft 10 The follow...

Page 12: ...3 correspond to phase se quence A B and C 19 Control circuit wiring for 3M condenser wa ter pump motor starter is shown for cooling only application For units with Flash Miniature Card Software Versio...

Page 13: ...of 0 1 ohm or less The grounding conductors must be capable of handling anticipated ground fault currents There must be a jumper cable 11 across the ground bus floor sill between any shipping splits...

Page 14: ...Make sure that elec tronic component damage is avoided during the welding process Keep the welded return path as close as possible to the work position The return path must always be within 3 ft of t...

Page 15: ...JOHNSON CONTROLS 15 Section 2 Equipment grounding Form 160 00 N6 Issue date 08 27 2021 2 Figure 1 Grounding details LD14345 Equipment grounding cont d...

Page 16: ...0 N6 Issue date 08 27 2021 Section 2 Equipment grounding Unit dimensional details 74 in x 44 in x 104 in Figure 2 Unit dimensions 74 in x 44 in x 104 in LD14422 I Input M Motor C Controls C Oil Pump 4...

Page 17: ...ipment grounding Form 160 00 N6 Issue date 08 27 2021 2 Unit dimensional details 122 in x 44 in x 104 in Figure 3 Unit dimensions 122 in x 44 in x 104 in LD14423 I Input M Motor C Controls C Oil Pump...

Page 18: ...6 Issue date 08 27 2021 Section 2 Equipment grounding Unit dimensional details 164 in x 50 in x 104 in Figure 4 Unit dimensions 164 in x 50 in x 104 in LD14424 I Input M Motor C Controls C Oil Pump 46...

Page 19: ...pment grounding Form 160 00 N6 Issue date 08 27 2021 2 Unit dimensional details 174 in x 50 in x 104 in Figure 5 Unit dimensions 174 in x 50 in x 104 in LD14425 I I I Input M Motor C Controls C Oil Pu...

Page 20: ...THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS 20 Form 160 00 N6 Issue date 08 27 2021...

Page 21: ...or s has ample clearance and all of the controls are accessible Failure to remove power factor correction or surge capacitors from the load side of the drive can result in serious damage to the equipm...

Page 22: ...esult in serious electrical failure which is not covered by warranty If the appli cation is greater than 5000 ft 1524 m above sea level the drive must be reviewed as a special quote For ad ditional de...

Page 23: ...onnel must install this equipment Install the unit in a secure upright position in a well ventilated area A noncombustible insulating floor or mat must be provided in the area immediately surrounding...

Page 24: ...d a shielded communications cable The six conduc tors are for the following GND Ground L 120 VAC control power line side 2 120 VAC control power neutral side 24 120 VAC start signal from panel to MVVS...

Page 25: ...lectrode to the MV VSD ground bus or ground terminal 2 If not already provided by the factory a main bonding jumper must be installed from the incoming grounded connector bus neutral to the ground bus...

Page 26: ...tions 24 16 53 L 2 R24 67 68 69 GND See Table 4 Table 5 and Table 6 for wire numbers and termination points for YK YD and YKEP units respectively Table 4 Control and oil pump wire numbers and terminat...

Page 27: ...he MVVSD Check connections Although the equipment and devices have been completely tested at the fac tory a final field check must be made that all elec trical wiring and bus bar connections are corre...

Page 28: ...that the MVVSD and associated field wir ing are free from short circuits and grounds The preferred method is to perform a dielectric test at 2 25 times the nominal system voltage plus 2 000 V This mu...

Page 29: ...osed With all removable barriers in place and all doors closed and latched the devices must be turned on with a firm positive motion Protective devices and switches that are not quick acting must not...

Page 30: ...JOHNSON CONTROLS 30 Form 160 00 N6 Issue date 08 27 2021 NOTES...

Page 31: ...5556 5 6 C range Table 7 SI metric conversion Measurement Multiply English unit By factor To obtain metric unit Capacity Tons Refrigerant Effect ton 3 516 Kilowatts kW Power Horsepower 0 7457 Kilowat...

Page 32: ...Pennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2021 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 00 N6 821 Issue Date Augus...

Reviews: