FORM 150.72-EG6 (516)
JOHNSON CONTROLS
27
LD18433
YLAA0070SE, YLAA0080SE, YLAA0089SE
Unit Dimensions (Cont'd)
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;
however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.