JOHNSON CONTROLS
FORM 150.72-EG6 (516)
46
YLAA VOLT
HZ
MCA
MIN
N/F
DISC
SW
MIN
DUAL
ELEM
FUSE
& CB
MAX
DUAL
ELEM
CB
SYSTEM # 1
COMPR 1
COMPR 2
COMPR 3
STD FLOW FANS
RLA LRA RLA LRA RLA
LRA QTY FLA
LRA
101
208
60
458
600
500
500
57.7
284
57.7
284
57.7
284
2
7.6
44
230
60
456
600
500
500
57.7
330
57.7
330
57.7
330
2
7.4
37
380
60
264
400
300
300
30.9
192
30.9
192
30.9
192
2
4.5
23.1
460
60
224
400
250
250
26.9
180
26.9
180
26.9
180
2
4
19
575
60
178
250
200
200
21.5
132
21.5
132
21.5
132
2
2.9
15.3
120
208
60
497
800
600
600
106.2 523 106.2 523
3
7.6
44
230
60
496
800
600
600
106.2 578 106.2 578
3
7.4
37
380
60
300
400
350
350
64.3
355
64.3
355
3
4.5
23.1
460
60
250
400
300
300
53.1
290
53.1
290
3
4
19
575
60
198
250
225
225
42.5
255
42.5
255
3
2.9
15.3
125
208
60
512
800
600
600
106.2 523 106.2 523
4
7.6
44
230
60
511
800
600
600
106.2 578 106.2 578
4
7.4
37
380
60
309
400
350
350
64.3
355
64.3
355
4
4.5
23.1
460
60
258
400
300
300
53.1
290
53.1
290
4
4
19
575
60
204
250
225
225
42.5
255
42.5
255
4
2.9
15.3
136
208
60
579
800
600
600
106.2 523 106.2 523 106.2
523
4
7.6
44
230
60
577
800
600
600
106.2 578 106.2 578 106.2
578
4
7.4
37
380
60
338
600
400
400
64.3
355
64.3
355
64.3
355
4
4.5
23.1
460
60
285
400
300
300
53.1
290
53.1
290
53.1
290
4
4
19
575
60
226
400
250
250
42.5
255
42.5
255
42.5
255
4
2.9
15.3
142
208
60
579
800
600
600
106.2 523 106.2 523 106.2
523
5
7.6
44
230
60
577
800
600
600
106.2 578 106.2 578 106.2
578
5
7.4
37
380
60
338
600
400
400
64.3
355
64.3
355
64.3
355
5
4.5
23.1
460
60
285
400
300
300
53.1
290
53.1
290
53.1
290
5
4
19
575
60
226
400
250
250
42.5
255
42.5
255
42.5
255
5
2.9
15.3
155
208
60
618
800
700
700
106.2 523 106.2 523 106.2
523
4
7.6
44
230
60
617
800
700
700
106.2 578 106.2 578 106.2
578
4
7.4
37
380
60
374
600
400
400
64.3
355
64.3
355
64.3
355
4
4.5
23.1
460
60
311
400
350
350
53.1
290
53.1
290
53.1
290
4
4
19
575
60
246
400
300
300
42.5
255
42.5
255
42.5
255
4
2.9
15.3
156
208
60
634
800
700
700
106.2 523 106.2 523 106.2
523
6
7.6
44
230
60
632
800
700
700
106.2 578 106.2 578 106.2
578
6
7.4
37
380
60
383
600
400
400
64.3
355
64.3
355
64.3
355
6
4.5
23.1
460
60
319
400
350
350
53.1
290
53.1
290
53.1
290
6
4
19
575
60
252
400
300
300
42.5
255
42.5
255
42.5
255
6
2.9
15.3
170
208
60
740
1000
800
800
106.2 523 106.2 523 106.2
523
5
7.6
44
230
60
738
1000
800
800
106.2 578 106.2 578 106.2
578
5
7.4
37
380
60
447
600
500
500
64.3
355
64.3
355
64.3
355
5
4.5
23.1
460
60
372
600
400
400
53.1
290
53.1
290
53.1
290
5
4
19
575
60
295
400
350
350
42.5
255
42.5
255
42.5
255
5
2.9
15.3
175
208
60
740
1000
800
800
106.2 523 106.2 523 106.2
523
5
7.6
44
230
60
738
1000
800
800
106.2 578 106.2 578 106.2
578
5
7.4
37
380
60
447
600
500
500
64.3
355
64.3
355
64.3
355
5
4.5
23.1
460
60
372
600
400
400
53.1
290
53.1
290
53.1
290
5
4
19
575
60
295
400
350
350
42.5
255
42.5
255
42.5
255
5
2.9
15.3
Electrical Data Without Pumps (Cont'd)
NOTES:
1. Reference PIN 59 for pump models.
2. Use this table along with Pump Electrical Data
on page 46
to determine electrical data of the unit plus the pump.
3. Does not include the Control Transformer.
on page 41
)
Summary of Contents for YLAA
Page 4: ...JOHNSON CONTROLS FORM 150 72 EG6 516 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...FORM 150 72 EG6 516 JOHNSON CONTROLS 35 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 48: ...JOHNSON CONTROLS FORM 150 72 EG6 516 48 Wiring Diagram ...
Page 49: ...FORM 150 72 EG6 516 JOHNSON CONTROLS 49 LD18444 Wiring Diagram Cont d ...