SECTION 6 – COMMISSIONING
Leave all other settings not listed in the following table in their default values.
TABLE 13 -
DRIVE PROGRAMMING PARAMETERS
PARAMETER CODE
DESCRIPTION
SETTING
9902
Function Select
0
9905
Motor Rated Voltage
See motor nameplate
(208 V, 230 V, 460 V)
9906
Motor Rated Current
See motor nameplate
9907
Motor Frequency
See motor nameplate
(50 Hz, 60 Hz)
1103
Command Source Mode
0
1300
Analog Input 1 Signal Format
U 0-10
1301
Analog Input 1 Offset
23.5
1302
Analog Input 1 Scaling
1850
2007
Min Frequency Limit
0
2008
Max Frequency Limit
See motor nameplate
(50 Hz, 60 Hz)
2102
Stop Mode
0
2202
Accel Time
30.0
2203
Decel Time
30.0
2601
Energy Optimizer
0
GROUP NAVIGATION
PARAMETER STRUCTURE
LD29434
FIGURE 37 -