SECTION 7 – UNIT CONTROLS
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
7
TABLE 17 -
PROGRAM KEY LIMITS AND DEFAULT
PROGRAM VALUE
MODE
LOW LIMIT HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
—
325 psig
575 psig
570 psig
22.40 barg
39.60 barg
39.30 barg
SUCTION PRESSURE CUTOUT
WATER COOLING
80 psig
120 psig
80 psig
5.52 barg
8.27 barg
5.52 barg
GLYCOL COOLING
33 psig
120 psig
44 psig
2.28 barg
8.27 barg
3.03 barg
LOW AMBIENT TEMP. CUTOUT
STANDARD AMBIENT
25.0°F
60.0°F
25.0°F
-3.9°C
15.6°C
-3.9°C
LOW AMBIENT
0.0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
VSD FAN
-10.0°F
60.0°F
25.0°F
-23.3°C
15.6°C
-3.9°C
ALL OTHER CONFIGURATIONS
0.0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
LEAVING CHILLED LIQUID
TEMP. CUTOUT
WATER COOLING
—
—
36°F
2.2°C
GLYCOL COOLING
8.0°F
36.0°F
36.0°F
-13.3°C
2.2°C
2.2°C
LOW TEMPERATURE
GLYCOL COOLING
-1.0°F
36.0°F
36.0°F
-18.3°C
2.2°C
2.2°C
ANTI-RECYCLE TIMER
—
300 s
600 s
600 s
FAN CONTROL ON PRESSURE
—
360 psig
485 psig
385 psig
24.80 barg
33.40 barg
26.50 barg
FAN DIFFERENTIAL OFF PRESSURE
—
80 psid
160 psid*
125 psid
5.51 bard
11.03 bard*
8.62 bard
TOTAL NUMBER OF COMPRESSORS
SINGLE SYSTEM
2
3
3
DUAL SYSTEM
4
6
6
NUMBER OF FANS PER SYSTEM
—
2
4
3
UNIT/SYSTEM TRIP VOLTS
CURRENT FEEDBACK
0.5 V
4.5 V
2.5 V
REMOTE UNIT ID
—
0
7
0
SYSTEM 1 AND SYSTEM 2
SUPERHEAT SETPOINTS
R-410a
5.0°F
18.0°F
9.0°F
2.8°C
10.0°C
5.0°C
DUTY/STANDBY PUMP CHANGE OVER
R-410a
1
30
30
ANTI-VACUUM SUCTION PRESSURE
CUTOUT
R-410a
3 psig
20 psig
10%
programmed
suction cutout
0.21 barg
1.38 barg
ANTI-VACUUM DELAY TIME
R-410a
3 s
30 s
6 s
VSD FAN LOW PRESSURE LIMIT
R-410a
247 psig
345 psig
247 psig
17.03 barg
23.78 barg
17.03 barg
VSD FAN HIGH PRESSURE LIMIT
R-410a
350 psig
450 psig
450 psig
24.13 barg
31.03 barg
31.03 barg
VSD FAN LOW AMBIENT
DISCHARGE PRESSURE SETPOINT
R-410a
360 psig
420 psig
390 psig
24.82 barg
28.96 barg
26.89 barg
VSD FAN LOW AMBIENT DISCHARGE
PRESSURE CONTROL RANGE
R-410a
60 psig
120 psig
90 psig
4.14 barg
8.27 barg
6.21 barg
* The minimum discharge pressure allowed is 235 psig. The Fan Differential Off Pressure High Limit will be lowered (reduced) to prevent go
-
ing below 235 psig based on where the fan control On Pressure is programmed.