JOHNSON CONTROLS
50
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
SECTION 5 – TECHNICAL DATA
REFRIGERANT R-410A
YLAA
STANDARD EFFICIENCY UNITS
0070SE 0080SE 0089SE 0100SE 0120SE 0136SE 0155SE 0170SE
NOMINAL RATINGS
3
TONS
71.0
77.8
81.8
95.6
118.1
126.1
143.0
167.4
KW INPUT
77.5
86.3
93.0
111.5
134.6
142.6
165.0
192.1
EER
10.4
10.0
9.8
9.7
9.8
9.7
9.7
9.7
IPLV
16.1
15.6
15.8
14.5
15.0
15.8
15.8
15.6
GENERAL UNIT DATA
Length
116.1
116.1
116.1
142.7
142.7
187.7
187.7
232.7
Width
88
88
88
88
88
88
88
88
Height
94.2
94.2
94.2
94.2
94
94.2
94.2
94.2
Number Of Refrigerant Circuits
2
2
2
2
2
2
2
2
REFRIGERANT CHARGE, OPERATING
R-410A, CKT1/CKT2, lb
43/43
47/44
57/57
55/58
54/62
75/71
75/70
90/87
Oil Charge, CKT1/CKT2, gal
2.58/2.58 3.28/2.58 3.28/2.76 3.28/3.33 3.33/3.33 4.99/2.76 4.99/3.33 4.99/4.99
Shipping Weight
3578
3898
4168
4791
5183
6148
6414
7734
Operating Weight
3623
3954
4241
4864
5293
6232
6524
7818
COMPRESSORS, SCROLL TYPE
Compressors Per Circuit
3/3
3/3
3/3
3/2
2/2
3/3
3/2
3/3
Compressors Per Unit
6
6
6
5
4
6
5
6
NOMINAL TONS PER COMPRESSOR
Circuit 1
13
15
15
15
32
32
32
32
Circuit 2
13
13
15
32
32
15
32
32
CONDENSER
Total Face Area Ft
2
106.9
106.9
106.9
133.6
160.3
213.8
213.8
267.2
Number Of Rows
1
1
1
1
1
1
1
1
Fins Per Inch
20
20
20
20
20
20
20
20
CONDENSER FANS, LOW SOUND
Number Of Fans, CKT 1/CKT 2
2/2
2/2
2/2
3/2
3/3
4/4
4/4
5/5
Fan HP
2
2
2
2
2
2
2
2
Fan RPM
1160
1160
1160
1160
1160
1160
1160
1160
Total Chiller CFM
60000
60000
60000
75000
90000
120000
120000
150000
EVAPORATOR
Water Volume, gal
5.4
6.7
8.8
8.8
13.2
10.0
13.2
10.0
Maximum Water Side Pressure,
psig
150
150
150
150
150
150
150
150
Maximum Refrigerant Side
Pressure, psig
450
450
450
450
450
450
450
450
Minimum Chiller Water Flow
Rate, GPM
60
100
100
100
150
150
150
150
Maximum Chiller Water Flow
Rate, GPM
285
355
385
385
625
625
625
625
Water Connections Size, in.
3
3
3
3
3
4*
4*
4*
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Addition
al rating information can be provided by your local Johnson Controls Sales Office.
PHYSICAL DATA YLAA0041 – YLAA0230 60 HZ
TABLE 6 -
PHYSICAL DATA (ENGLISH) 60 HZ