JOHNSON CONTROLS
51
SECTION 5 – TECHNICAL DATA
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
55
TABLE 6 -
PHYSICAL DATA (ENGLISH) 60 HZ (CONT’D)
REFRIGERANT R-410A
YLAA
HIGH EFFICIENCY UNITS
0041HE
0048HE
0058HE 0065HE
0081HE
0082HE
0092HE
0101HE
NOMINAL RATINGS
3
TONS
39.5
48.9
57.0
62.3
78.8
77.9
85.7
98.3
KW INPUT
34.1
47.0
57.7
65.2
91.0
90.9
83.6
106.1
EER
11.6
10.9
10.6
10.4
10.4
10.3
11.0
10.1
IPLV
16.7
15.73
15.6
15.6
16.1
16.1
16.1
15.7
GENERAL UNIT DATA
Length
100.2
100.2
100.2
100.2
100.2
100.2
142.7
142.7
Width
88.0
88.0
88.0
88.0
88.0
88.0
88.0
88.0
Height
94.2
94.2
94.2
94.2
94.2
94.2
94.2
94.2
Number Of Refrigerant Circuits
2
2
2
2
2
2
2
2
REFRIGERANT CHARGE, OPERATING
R-410A, CKT1/CKT2, lb
40/40
40/42
43/43
43/43
44/44
44/44
59/55
45/65
Oil Charge, CKT1/CKT2, gal
0.86/0.86 0.86/0.86 2.58/2.58 2.89/2.58 2.58/2.58 2.58/2.58 2.76/2.76 3.28/3.33
Shipping Weight
3855
3724
3508
3704
4061
4213
4718
4953
Operating Weight
3877
3754
3552
3748
4145
4295
4791
5026
COMPRESSORS, SCROLL TYPE
Compressors Per Circuit
2/2
2/2
2/2
3/2
3/3
3/3
3/3
3/2
Compressors Per Unit
4
4
4
5
6
6
6
5
NOMINAL TONS PER COMPRESSOR
Circuit 1
10
13
15
13
15
15
15
15
Circuit 2
10
13
15
15
13
13
15
32
CONDENSER
Total Face Area Ft
2
106.9
106.9
106.9
106.9
106.9
106.9
160.3
160.3
Number Of Rows
1
1
1
1
1
1
1
1
Fins Per Inch
20
20
20
20
20
20
20
20
CONDENSER FANS, LOW SOUND
Number Of Fans, CKT 1/CKT 2
2/2
2/2
2/2
2/2
2/2
2/2
3/3
4/2
Fan HP
2
2
2
2
2
2
2
2
Fan RPM
1160
1160
1160
1160
1160
1160
1160
1160
Total Chiller CFM
26800
60000
60000
60000
62400
62400
90000
90000
EVAPORATOR
Water Volume, gal
2.57
3.57
5.4
5.4
10
10
8.8
8.8
Maximum Water Side Pressure,
psig
150
150
150
150
150
150
150
150
Maximum Refrigerant Side
Pressure, psig
450
450
450
450
450
450
450
450
Minimum Chiller Water Flow
Rate, GPM
41
48
60
60
150
100
100
100
Maximum Chiller Water Flow
Rate, GPM
224
224
285
285
625
385
385
385
Water Connections Size, in.
3
3
3
3
3
3
3
3
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Addition
al rating information can be provided by your local Johnson Controls Sales Office.