JOHNSON CONTROLS
52
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
SECTION 5 – TECHNICAL DATA
REFRIGERANT R-410A
YLAA
HIGH EFFICIENY UNITS
0125HE
0139HE
0142HE
0156HE
0175HE
0200HE
0230HE
NOMINAL RATINGS
3
TONS
116.0
126.1
129.5
144.5
172.5
194.5
220.6
KW INPUT
122.0
149.6
138.9
153.0
194.2
210.9
240.0
EER
10.3
10.1
10.2
10.2
9.8
10.1
10.2
IPLV
15.7
16.0
15.9
15.5
15.6
16.1
15.6
GENERAL UNIT DATA
Length
187.7
187.7
187.7
232.7
232.7
274.4
274.4
Width
88.0
88.0
88
88
88
88.3
88.3
Height
94.2
94.2
94.2
94.2
94.2
94.2
94.2
Number Of Refrigerant Circuits
2
2
2
2
2
2
2
REFRIGERANT CHARGE, OPERATING
R-410A, CKT1/CKT2, LB
75/71
76/76
83/73
90/82
94/92
95/95
100/100
Oil Charge, CKT1/CKT2, gal
3.33/3.33 4.20/2.80 4.99/2.76 4.99/3.33 4.99/4.99
4.2/4.2
4.99/4.99
Shipping Weight
5869
6380
6259
7344
7882
9205
9690
Operating Weight
5942
6488
6369
7428
8001
9333
9821
COMPRESSORS, SCROLL TYPE
Compressors Per Circuit
2/2
3/2
3/3
3/2
3/3
3/3
3/3
Compressors Per Unit
4
5
6
5
6
6
6
NOMINAL TONS PER COMPRESSOR
Circuit 1
32
25
32
32
32
35
40
Circuit 2
32
32
15
32
32
35
40
CONDENSER
Total Face Area Ft
2
213.8
213.8
213.8
267.2
267.2
320
320
Number Of Rows
1
1
1
1
1
1
1
Fins Per Inch
20
20
20
20
20
20
20
CONDENSER FANS, LOW SOUND
Number Of Fans, CKT 1/CKT 2
4/4
4/4
5/3
6/4
5/5
6/6
6/6
Fan HP
2
2
2
2
2
2.0
2.0
Fan RPM
1160
1160
1160
1160
1160
1160
1160
Total Chiller CFM
124800
124800
124800
150000
150000
180000
180000
EVAPORATOR
Water Volume, Gallons
8.8
13.2
13.2
10.0
14.3
12.6
14.3
Maximum Water Side Pressure, psig
150
150
150
150
150
150
150
Maximum Refrigerant Side
Pressure, psig
450
450
450
450
450
450
450
Minimum Chiller Water Flow Rate, GPM
100
150
150
150
150
230
230
Maximum Chiller Water Flow Rate, GPM
385
625
625
625
625
625
650
Water Connections Size, in.
4*
4*
4*
4*
4*
5
5
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Addition
al rating information can be provided by your local Johnson Controls Sales Office.
TABLE 6 -