JOHNSON CONTROLS
60
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
SECTION 5 – TECHNICAL DATA
CHILLER
MODEL
VOLTAGE
CODE
MIN CKT.
AMPS
MIN N/F
DISC SW
MIN DUAL
ELEM
FUSE AND
MIN CB
MAX DUAL
ELEM
FUSE
MAX CB
156
208
634
800
700
700
230
632
800
700
700
380
383
600
400
400
460
319
400
350
350
575
252
400
300
300
170
208
740
1000
800
800
230
738
1000
800
800
380
447
600
500
500
460
372
600
400
400
575
295
400
350
350
175
208
740
1000
800
800
230
738
1000
800
800
380
447
600
500
500
460
372
600
400
400
575
295
400
350
350
200
208
734
1000
800
800
230
731
1000
800
800
380
443
600
500
500
460
369
600
400
400
575
292
400
300
300
230
208
959
1200
1000
1000
230
956
1200
1000
1000
380
599
600
600
600
460
504
600
600
600
575
359
600
400
400
TABLE 11 -
ELECTRICAL DATA WITHOUT PUMPS (CONT’D)