JOHNSON CONTROLS
92
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
SECTION 5 – TECHNICAL DATA
FOUR FAN UNITS
DIMENSIONS – YLAA0041HE, YLAA0048HE, YLAA0058HE, YLAA0065HE,
YLAA0081HE, YLAA0082HE
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
FIGURE 27 -
FOUR FAN UNITS DIMENSIONS – YLAA0041HE, YLAA0048HE, YLAA0058HE, YLAA0065HE,
YLAA0081HE, YLAA0082HE
035-24059-001 REV-E
LD23531
1678 [66.1]
1117 [44.0]
POWER ENTRY
330.2 [13.00] WIDE X 177.8 [7.00] HIGH
CONTROL PANEL BOTTOM DETAIL
1177 [46.4]
1097 [43.2]
1669 [65.7]
201 [0.8
]
822 [32.4]
254 [10.0]
1085 [42.7]
1595 [62.8]
2251 [88.6]
2398 [94.4]
OVERALL HEIGHT
FRAME HEIGHT
2077 [81.8]
82 [3.2
]
DISCONNECT SWITCH
(OPTIONAL)
51 [2.0]
2242 [88.3]
FRAME WIDTH
OVERALL WIDTH
2254 [88.8]
2627 [103.4]
2180 [85.8]
442 [17.4]
442 [17.4]
WATER CONNECTIONS
OVERALL LENGTH
333 [13.1]
1884 [74.2]
16 [5/8”]
MOUNTING
HOLES TYP
MOUNTING
HOLES TYP
MOUNTING
HOLES TYP
WATER CONNECTION
36 [1.4]
36 [1.4]
269 [10.6]
3” VICTAULIC
INLET