Johnson Controls
61
Section 5: Technical data
Form 150.72-ICOM6
Issue date: 12/19/2023
55
Table 11:
Electrical data without pumps, R-410A, continued
YLAA
V
Hz MCA Min. N/F
disc SW
Min. dual
elem. fuse
and CB
Max. dual
elem. CB
System 1
Compr. 1
Compr. 2
Compr. 3
Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
155
208
60
618
800
700
700
106.2 523 106.2 523 106.2 523
4
7.6
44
230
60
617
800
700
700
106.2 578 106.2 578 106.2 578
4
7.4
37
380
60
374
600
400
400
64.3
355
64.3
355
64.3
355
4
4.5
23.1
460
60
311
400
350
350
53.1
290
53.1
290
53.1
290
4
4
19
575
60
246
400
300
300
42.5
255
42.5
255
42.5
255
4
2.9
15.3
156
208
60
634
800
700
700
106.2 523 106.2 523 106.2 523
6
7.6
44
230
60
632
800
700
700
106.2 578 106.2 578 106.2 578
6
7.4
37
380
60
383
600
400
400
64.3
355
64.3
355
64.3
355
6
4.5
23.1
460
60
319
400
350
350
53.1
290
53.1
290
53.1
290
6
4
19
575
60
252
400
300
300
42.5
255
42.5
255
42.5
255
6
2.9
15.3
170
208
60
740
1,000
800
800
106.2 523 106.2 523 106.2 523
5
7.6
44
230
60
738
1,000
800
800
106.2 578 106.2 578 106.2 578
5
7.4
37
380
60
447
600
500
500
64.3
355
64.3
355
64.3
355
5
4.5
23.1
460
60
372
600
400
400
53.1
290
53.1
290
53.1
290
5
4
19
575
60
295
400
350
350
42.5
255
42.5
255
42.5
255
5
2.9
15.3
175
208
60
740
1,000
800
800
106.2 523 106.2 523 106.2 523
5
7.6
44
230
60
738
1,000
800
800
106.2 578 106.2 578 106.2 578
5
7.4
37
380
60
447
600
500
500
64.3
355
64.3
355
64.3
355
5
4.5
23.1
460
60
372
600
400
400
53.1
290
53.1
290
53.1
290
5
4
19
575
60
295
400
350
350
42.5
255
42.5
255
42.5
255
5
2.9
15.3
200
208
60
734
1,000
800
800
102.8 574 102.8 574 102.8 574
6
7.6
44
230
60
731
1,000
800
800
102.8 635 102.8 635 102.8 635
6
7.4
37
380
60
443
600
500
500
62.2
355
62.2
355
62.2
355
6
4.5
23.1
460
60
369
600
400
400
51.4
280
51.4
280
51.4
280
6
4
19
575
60
292
400
300
300
41.1
225
41.1
225
41.1
225
6
2.9
15.3
230
208
60
959
1,200
1,000
1,000
138.8 943 138.8 943 138.8 943
6
7.6
44
230
60
956
1,200
1,000
1,000
138.8 943 138.8 943 138.8 943
6
7.4
37
380
60
599
800
600
600
87.2
564
87.2
564
87.2
564
6
4.5
23.1
460
60
504
600
600
600
73
408
73
408
73
408
6
4
19
575
60
359
600
400
400
51.9
375
51.9
375
51.9
375
6
2.9
15.3
Notes:
• Reference PIN 59 for pump models.
• Use this table along with Table 9 on page 58 to determine electrical data of the unit plus the pump.
• Does not include the control transformer.