JOHNSON CONTROLS
92
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
SECTION 6 – COMMISSIONING
FORM 150.73-CL2
ISSUE DATE: 10/29/2012
4. Put the unit into Service Mode (as described
under the Control Service and Troubleshooting
section) and cycle each condenser fan to ensure
proper rotation. ...................................................
5. Prior to this step, turn system 2 off (if applicable
–refer to
YLUA - Installation, Operation,
Maintenance Manual (Form 150.73-NM1)
Unit
Keys, Option 2 for more information on system
switches). Connect a manifold gauge to system
1 suction and discharge service valves. ............
Place the Unit Switch in the control panel
to the “ON” position. As each compressor
cycles on, ensure that the discharge pressure
rises and the suction pressure decreases. If
this does not occur, the compressor being
tested is operating in the reverse direction
and must be corrected. After verifying proper
compressor rotation, turn the Unit Switch to “OFF.”
The discharge air or suction pressure
setpoint may need to be temporarily
lowered to ensure all compressors cycle
“on.”
This unit uses scroll compressors
which can only operate in one direc-
tion. Failure to observe this will lead
to compressor failure.
6. Turn system 1 “off” and system 2 “on” (refer to
YLUA - Installation, Operation, Maintenance
Manual (Form 150.73-NM1)
Unit Keys, Option 2
for more information on system switches). ........
Place the Unit Switch in the control panel to
the “ON” position. As each compressor cycles
“ON”, ensure that the discharge pressure
rises and the suction pressure decreases. If
this does not occur, the compressor being
tested is operating in the reverse direction
and must be corrected. After verifying proper
compressor rotation, turn the Unit Switch to “OFF”.
The chilled liquid setpoint may need
to be temporarily lowered to ensure all
compressors cycle “ON”.
3. Program/verify the Cooling Setpoints, Program
Setpoints, and unit Options. Record the values
below. .................................................................
OPTIONS
Display Language
SYS 1 Switch
Sys 2 Switch
Chilled Liquid
*
Ambient Control
Local/Remote Mode
Control Mode
Display Units
*
Lead/Lag Control
*
Fan Control
Manual Override
Current Feedback
**
Soft Start
**
Unit Type
**
Refrigerant Type
**
Expansion Valve Type
COOLING SETPOINTS
Cooling Setpoint
Range
EMS-PWM Max. Setpoint
PROGRAM
Discharge Pressure Cutout
Suct. Pressure Cutout
Low Amb. Temp. Cutout
Anti-Recycle Time
Fan Control On Pressure
Fan Differential Off Pressure
Total # of Compressors
*
Number of Fans/System
*
Unit/Sys Voltage
Unit ID
*
Sys 1 Superheat Setpoint
*
Sys 2 Superheat Setpoint
* Not On All Models
** Viewable Only
Summary of Contents for YLUA0248 Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...