SECTION 10 – MAINTENANCE
Received Data (Control Data)
The unit receives 8 data values from the ISN. The first
4 are analog values and the last 4 are digital values.
These 8 data values are used as control parameters
when in REMOTE mode. When the unit is in LOCAL
mode, these 8 values are ignored. If the unit receives
no valid ISN transmission for 5 minutes it will revert
back to all local control values.
lists the 5 control parameters. These values are found
under feature 54 on the ISN.
ISN CONTROL
TABLE 33 -
ISN TRANSMITTED DATA
ISN
PAGE
CHARACTER
TYPE
DATA
P11
8-11
Analog Leaving Chilled
Liquid Temp.
P12
12-15
Analog Return Chilled
Liquid Temp.
P13
16-19
Analog
----
P14
20-23
Analog
----
P15
24-27
Analog SYS 1 Suction
Temp. (EEV Only)
P16
28-31
Analog Ambient Air Temp.
P17
32-35
Analog
SYS 1 Suction
Superheat
(EEV Only)
P18
36-39
Analog SYS 1 Run Time
(Seconds)
P19
40-43
Analog SYS 1 Suction
Pressure
P20
44-47
Analog SYS 1 Discharge
Pressure
P21
48-51
Analog
----
P22
52-55
Analog
----
P23
56-59
Analog
SYS 1 EEV
Output %
(EEV Only)
P24
60-63
Analog SYS 1
Anti-Recycle Timer
P25
64-67
Analog Anti-Coincidence
Timer
P26
68-71
Analog SYS 2 Suction
Temp. (EEV Only)
P27
72-75
Analog SYS 2 Run Time
(Seconds)
P28
76-79
Analog SYS 2
Suction Pressure
P29
80-83
Analog SYS 2
Discharge Pressure
P30
84-87
Analog
----
P31
88-91
Analog
----
P32
92-95
Analog
SYS 2
Suction Superheat
(EEV Only)
P33
96-99
Analog SYS 2
Anti-Recycle Timer
P34
100-103
Analog
SYS 2 EEV
Output %
(EEV Only)
P35
104-107
Analog # of Compressors
P36
108
Digital SYS 1 Alarm
P37
109
Digital SYS 2 Alarm
Transmitted Data
After receiving a valid transmission from the ISN, the
unit will transmit either operational data or history buf-
fer data depending on the “History Buffer Request” on
ISN PAGE 10. Data must be transmitted for every ISN
page under feature 54. If there is no value to be sent to
a particular page, a zero will be sent.
show the data values
and page listings for this unit.
ISN PAGES listed are ENG PAGE
REFERENCES and must be decoded
to the corresponding PAGE REF
point map related to the communica-
tions protocol type utilized. The latest
point map information is listed on the
Johnson Controls Group Equipment
Integration website.
TABLE 32 -
ISN RECEIVED DATA
ISN
CONTROL DATA
PAGE
P03
SETPOINT
COOLING
P04
LOAD LIMIT STAGE (0,1, 2)
P05
–
P06
–
P07
START/STOP COMMAND
(0 = STOP, 1 = RUN)
P08
—
P09
—
P10
HISTORY BUFFER REQUEST
(0 = CURRENT DATA, 1 = LAST HISTORY DATA)
Summary of Contents for YLUA0248 Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...