JOHNSON CONTROLS
17
Form 160.78-O1
Issue date: 05/19/2021
3
Section 3 - Maintenance
Renewal parts
For any required Renewal Parts, refer to the
YMC
2
Unit
Renewal Parts Manual (Form 160.78-RP1).
Checking system for leaks
Leak testing during operation
The refrigerant side of the system is carefully pressure
tested and evacuated at the factory.
After the system has been charged, the system should
be carefully leak tested with a R-134a compatible leak
detector to be sure all joints are tight.
If any leaks are indicated, they must be repaired im-
mediately. Usually, leaks can be stopped by tighten-
ing flare nuts or flange bolts. However, for any major
repair, the refrigerant charge must be removed. See
Handling refrigerant for dismantling and repairs
this section.
Conducting R-22 pressure test
With the R-134a charge removed and all known leaks
repaired, the system should be charged with a small
amount of R-22 mixed with dry nitrogen so that a ha-
lide torch or electronic leak detector can be used to de-
tect any leaks too small to be found by the soap test.
To test with R-22, complete the following steps:
1. With no pressure in the system, charge R-22 gas
into the system through the charging valve to a
pressure of 2 psig (14 kPa).
2. Build up the system pressure with dry nitrogen
to approximately 75 psig to 100 psig (517 kPa to
690 kPa). To be sure that the concentration of re-
frigerant has reached all parts of the system test
for the presence of refrigerant with a leak detector
at an appropriate service valve.
3. Test around each joint and factory weld. It is im-
portant that this test be thoroughly and carefully
done, spending as much time as necessary and us-
ing a good leak detector.
4. To check for refrigerant leaks in the evaporator
and condenser, open the vents in the evaporator
and condenser heads and test for the presence of
refrigerant. If no refrigerant is present, the tubes
and tube sheets may be considered tight. If refrig-
erant is detected at the vents, remove the heads,
locate the leak using a soap test or leak detector,
and repair the leak.
Figure 5 -
Evacuation of chiller
LD00949
Summary of Contents for YMC2 A
Page 12: ...JOHNSON CONTROLS 12 Form 160 78 O1 Issue date 05 19 2021 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 16: ...JOHNSON CONTROLS 16 Form 160 78 O1 Issue date 05 19 2021 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 26: ...JOHNSON CONTROLS 26 Form 160 78 O1 Issue date 05 19 2021 THIS PAGE INTENTIONALLY LEFT BLANK ...