background image

14

JOHNSON CONTROLS

FORM 155.19-EG3 (1011)

A CPVC or fiberglass discharge pipe should run from the 

rupture disk to a drain. Steel is not recommended unless 

extra care is taken to support piping and isolate any stress 

from the rupture disk. The discharge pipe must sup port 

independent of the Two-Stage unit.

SOUND AND VIBRATION CONSIDERATIONS

Since the YPC unit generates very little vibration, vibration 

eliminating  mounts  are  not  usually  required.  However, 

when the machine is installed where even mild noise is 

a problem, mounts or pads should be used (see Fig. 2, 

p. 13). The use of anchoring bolts on the machine legs is 

not normally necessary.

THERMAL INSULATION

YPC units require thermal insulation (by others) on both 

hot and cold surfaces in order to achieve maximum ef

-

ficiency and prevent sweating. Required insulation area 

is tabulated on page 17.

STEAM
General

  –  The YPC unit is nominally rated for dry steam 

with minimal superheat, and a pressure of 115 PSIG (7.93 

bar) (at the steam valve). The inlet steam must not have a 

temperature higher than 363°F (183.9°C) and cannot have 

a saturation pressure higher than 128 PSIG (8.83 bar).

Pressure

  –  Since  a  lower  steam  saturation  pressure 

corresponds to a lower temperature in the generator, a 

YPC  chiller’s  available  capacity  varies  with  the  steam 

pressures at the steam valve. Fig. 3 on p. 14 graphically 

depicts the relationship between steam saturation pres

-

sure and available capacity.

Piping  –  The steam piping must follow the diagram found 

in Fig. 4 on p. 15. Beginning at the steam supply, a steam 

separator should be installed to ensure the unit receives 

only dry steam. A steam trap below the separator will allow 

draining of only condensate. Beyond the separator, a #50 

mesh strainer removes foreign matter from the steam. A 

regulator is only necessary if the steam supply pressure 

to the unit will exceed 128 PSIG (8.8 bar). The pressure 

relief valve should be set to open at 128 PSIG (8.83 bar). 

The Johnson Controls-supplied steam control valve must 

be no further than 200 inches (5 m) from the first-stage 

generator  steam  inlet  flange  in  order  to  minimize  the 

pressure drop from the valve exit to the generator inlet.

Dimension H1 is specified to prevent condensate back-

flow from the generator into the steam piping. Dimen sion 

H2 is specified to prevent excessive backpressure to the 

drain cooler. During factory testing, the unit is calibrated to 

provide design condensate flow to a con densate system 

operating at 15.0 PSIG (1 bar) (as measured immediately 

downstream of the Drain Solenoid Valve). To duplicate this 

condition in the field, an adjustable Condensate System 

Backpressure Valve (by others) must be installed such 

that:

   ∆PH2 + ∆P ∆PVALVE = 15.0 PSIG (1 bar)

   Where:

   ∆PH2 = Pressure drop due to height, H2

   ∆PPIPING = Pressure drop due to condensate piping,    

 

 

elbows, bends, etc.

   ∆PVALVE = Pressure drop due to Condensate Sys- 

 

 

tem Backpressure Valve

The drain cooler installed on the unit effectively elimi nates 

the need for an additional condensate cooler or a steam 

trap. The drain solenoid valve is a factory in stalled device 

to insure zero steam flow through unit during shutdown.

All  steam  piping  should  be  adequately  supported  and 

braced independent of the Two-Stage chiller. The sup port 

system must account for the expansion and con traction 

of steam piping, avoiding the imposition of strain on the 

chiller components.

Control Valve Sizing  –  Control valves are sized for each 

job based upon the available steam pressure, required 

steam  pressure  at  the  unit,  and  the  full  load  required 

steam flow. During start-up, Johnson Controls technicians 

estab lish the minimum load steam valve position (20%) 

and set the limit switch accordingly, eliminating possible 

problems at start up.

ELECTRICAL DATA

Table 2 contains unit electrical data. Total kW includes 

power requirements for the system solution and refrig erant 

pumps. All models have one solution pump, one solution 

Application Data  ‑ continued

FIG. 3  –

  CAPACITY  VS. INLET STEAM PRESSURE 

AVAILABLE

PSIG

 

28.6 42.9 57.2 71.5 85.8 100  115

bar 1.97 2.96 3.94 4.93 5.92 6.90  7.93

STEAM INLET PRESSURE

Summary of Contents for YPC

Page 1: ...FORM 155 19 EG3 1011 Model YPC Two Stage Steam Fired Absorption Chiller Style D Models YPC ST 14SC through YPC ST 19S 300 through 675 Tons 1050 through 2372 kW ...

Page 2: ...M 155 19 EG3 1011 1 Introduction 3 How It Works 4 Ratings 5 MicroComputer Control Center 6 Mechanical Specifications 8 Optional Features 11 Application Data 12 Dimensions 17 Nozzle Arrangement 14SC 18 Nozzle Arrangement 16SL and Larger 19 Guide Specifications 20 ...

Page 3: ...ximately 1 19 With today s energy and environmental considerations the YORK YPC Two Stage Steam Absorption Chiller is the ideal choice for a wide range of applications YPC Steam Chillers come equipped with the same sophisticated microprocessor controls found throughout Johnson Controls line of large tonnage chillers making the YPC Steam Chiller the smart est and most efficient absorber on the mark...

Page 4: ...ates the possibility of crystallization solidification by allowing the unit to operate at much lower solution concentration and temperatures than series flow systems 2 First stage Generator An outside steam source heats dilute LiBr 58 3 coming from the Solution Pump Heat Exchangers This produces hot refrigerant vapor which is sent to the Second Stage Generator leaving a concentrated solution 63 8 ...

Page 5: ...rough a metering valve and flows down to the Refrigerant Pump where it is pumped up the the top of the Evaporator Here the liquid is sprayed out as a fine mist over the Evapora tor tubes Due to the extreme vacuum 6 mm Hg in the Evaporator some of the refrigerant liquid evaporator creating the refrigerant effect This vacuum is created by hygroscopic action the strong affinity LiBr has for water in ...

Page 6: ...down and the operational parameters just prior to shutdown For a complete history printout of the last four shut downs and operational parameters just prior to shut down CAPACITY CONTROL When automatic capacity control is desired the Micro Computer Control Center automatically varies the steam flow rate to maintain the programmed leaving chilled water set point for cooling loads ranging from 20 to...

Page 7: ...ety Shutdown systems discussed in this section Also included is an operator interface concentration calculator When in the PROGRAM mode an operator can use the concentration calculator to determine concentration by inputting set of conditions The operator must input any two of three parameters bromide solution temperature saturation temperature and pressure and the micropanel will display the conc...

Page 8: ...ell closer to the generator contains the intermediate pressure section of the machine consist ing of the condenser and second stage generator The second stage generator is a drip type heat exchanger with 5 8 16 mm 0 025 0 6 mm wall copper tubing for the 14SC and 3 4 19 mm OD 0 028 0 7 mm wall for the 16SL and larger Generator and condenser are separated by baffling which prevents liquid carryover ...

Page 9: ... use of a eductor Noncondensibles are then stored in a purge chamber until they can be removed through the use of a purge pump The purge pump is an oil rotary two stage vacuum pump with a 1 4 HP 3 Phase ODP motor The chiller control panel includes a SmartPurge system that will automatically sense the amount of non conden sibles in the purge chamber and empty the tank whenever necessary The SmartPu...

Page 10: ... Security access code is provided for operator to pro gram setpoints or to choose local remote or service modes of operation Manual control of the steam valve position and all pumps is provided through separate buttons in the service mode of operation Data Logging All operating and setpoint information can be transmitted to a remote printer by others through the RS232 port in the control center to...

Page 11: ... and includes the following Water flow rates and temperatures Steam consumption rate System operating temperatures and pressures Absorber solution concentrations All liquid levels in the sightglasses Exact solution and refrigerant charge amount SPARE PUMPS A complete set of replacement solution and refrigerant pumps ships alongside the unit for local spare parts inventory REMOTE RESET CONTROLS Two...

Page 12: ...imen tation or organic growth These will hurt chiller perform ance and increase operating and maintenance costs Normally performance may be maintained by corrective water treat ment and periodic cleaning of tubes If water conditions exist which cannot be corrected by proper water treatment it may be necessary to provide a larger allowance for foul ing and or specify special material of constructio...

Page 13: ...nstalled in the tower water piping in the same manner as the chilled water flow switch above The YPC chiller is engineered for maximum effi ciency at both design and part load operation by taking advantage of the colder cooling tower water tempera tures which naturally occur in the winter months In its standard con figuration YPC absorbers can toler ate entering tower water temperatures as low as ...

Page 14: ...he Johnson Controls supplied steam control valve must be no further than 200 inches 5 m from the first stage generator steam inlet flange in order to minimize the pressure drop from the valve exit to the generator inlet Dimension H1 is specified to prevent condensate back flow from the generator into the steam piping Dimen sion H2 is specified to prevent excessive backpressure to the drain cooler ...

Page 15: ...rain cooler at approximately 15 PSIG 1 bar 180 F 82 2 C 4 Maximum inlet steam pressure 128 PSIG 8 83 bar 5 Automatic shutoff valve to be failsafe type 6 Both the steam supply and condensate drain pipes must be prop erly sized and pitched to prevent hammering 7 Steam control valve to be installed within 200 inches 5 m of the first stage generator steam inlet flange spray header pump and one refrige...

Page 16: ...0V 125A 250V 36 8 12 12 1 7 5 67 5 15 5 28 230 3PH 60Hz 75 8 100A 240V 100A 250V 36 8 12 12 1 5 4 3 66 6 15 5 50 380V 3PH 50Hz 41 3 60A 480V 60A 600V 19 7 7 0 9 2 6 36 5 16 2 46 460V 3PH 60Hz 38 60A 480V 50A 600V 18 4 6 6 0 8 2 2 33 4 15 5 19S 17 200 208V 3PH 60Hz 94 7 200A 240V 125A 250V 36 8 30 12 1 7 5 85 5 20 1 28 230 3PH 60Hz 93 8 100A 240V 125A 250V 36 8 30 12 1 5 4 3 84 6 20 1 50 380V 3PH 5...

Page 17: ...ION AREAS LBS NO CHARGE LBS SHIPPED W CHARGE INLET PIPE IN OUTLET PIPE IN 14SC 201 74 88 20900 22500 24300 2 5 3 4 16SL 235 89 103 30200 34150 37800 4 0 3 4 172 398 17S 235 89 103 31000 34950 38600 4 0 3 4 172 398 18S 274 90 109 36900 41600 45800 4 0 3 4 205 474 19S 314 90 109 44500 49600 54900 4 0 3 4 237 506 UNIT TYPE LENGTH1 mm A WIDTH mm B HEIGHT mm C RIGGING WEIGHT OPERATING WEIGHT kg STEAM2 ...

Page 18: ... Victualic couplings Factory installed class 150 ANSI B16 5 round slip on forged carbon steel with 1 16 raised face water flanged nozzles are optional Companion flanges nuts bolts and gaskets are not furnished 3 Connected piping should allow for removal of compact water box for tube access and cleaning 4 Tower water must enter the absorber first for proper performance EVAPORATOR NOZZLE ARRANGEMENT...

Page 19: ...langes or the use of ANSI AWWA C 606 couplings Factory installed class 150 ANSI B16 5 round slip on forged carbon steel with 1 16 inch raised face water flanged nozzles are optional Companion flanges nuts bolts and gaskets are not furnished 3 Connected piping should allow for removal of compact water box for tube access and cleaning 4 Tower water must enter the absorber first for proper performanc...

Page 20: ... tubing for the 14SC and 3 4 19 05mm OD 0 028 0 71mm wall for the 16SL and larger with enhanced surface as required to meet given capacity WATER BOXES Water boxes shall be removable to permit tube cleaning and replacement Water circuit tubing to be replaceable from either end of the chiller heater unit Stubout water connections having ANSI AWWA C 606 grooves shall be provided as standard ANSI flan...

Page 21: ...to be sized by the unit manu facturer in accordance with the specified steam pressure and flow requirements The steam valve shall be a cage type valve incorporat ing a carbon steel body and a teflon seat Valve link age actua tor motor assembly shall be capable of modu lating steam flow in a linear fashion from 20 to 100 of maximum design chiller steam input Valve shall be equipped with 150 lb ANSI...

Page 22: ...automatic restart is displayed manual restart is implied all system operating information dis played just prior to shutdown Warning Conditions MicroComputer Control Center Panel shall close warning contacts and generate a unique warning message whenever one of the following operating conditions is detected Low refrigerant temperature High generator temperature or pressure High or low entering cond...

Page 23: ...f all operating setpoint and shutdown informa tion to a remote printer printer supplied by others This transmission can occur as needed or automatically on predetermined intervals 0 1 to 25 5 hrs In the case of a safety or cycling shutdown the RS 232 port shall transmit all operating data detected prior to the shut down as well as the time and cause of the shutdown to a remote printer printer supp...

Page 24: ... Form 155 19 EG3 1011 Supersedes 155 19 EG3 311 ...

Reviews: