YORK INTERNATIONAL
138
FORM 160.55-O1 (920)
Troubleshooting
SECTION 7
TROUBLE SHOOTING
TABLE 1
– CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE
CONTROL CENTER DISPLAY
CONTROL CENTER DISPLAY
GOVERNING CONTROL FUNCTION
DAY OF
TIME
CAUSE OF
METHOD OF
DESCRIPTION
OPERATING POINT
WEEK
OF DAY
SHUTDOWN
RESTART
ON RISE
ON FALL
MON. 10:00 AM
Low Water
Autostart
Low Water (LWT)
Chilled water
4°F below chilled
Temperature
setpoint
water setpoint
MON. 10:00 AM
Low Water
Autostart
Low Water (LWT)
Chilled water
4°F below chilled
Temperature VSD
setpoint
water setpoint
MON. 10:00 AM
Flow Switch
Autostart
Flow Switch
MON. 10:00 AM
System Cycling
Autostart
A remote command
(computer relay contact or
manual switch)
MON. 10:00 AM
Multi-Unit Cycling
Autostart
(Optional)
Lead-Lag Sequence Control
MON. 10:00 AM
Internal Clock
Autostart
Internal Clock
MON. 10:00 AM
AC Undervoltage
Autostart
<15% FLA for 25
continuous seconds
MON. 10:00 AM
Power Fault
Autostart
CM-2 Current Module or
Solid State Starter
Remote Stop
Energy Management System
MON.
Anti-Recycle,
Anti-Recycle
20 Min. Left
Timer
MON. 10:00 AM
Low Evap. Press.
Low Evap. Pressure
5.43 PSIA
5.42 PSIA
Transducer (LEP)
MON. 10:00 AM
Low Evap. Press.
LEP external control
Set to Job Spec.
Set to Job Spec.
Brine
(Brine units only)
MON. 10:00 AM
Low Oil
Low Oil Press. Transducer (OP)
20 PSID
15 PSID
Pressure
High Oil Press. Transducer (OP)
MON. 10:00 AM
High Pressure
High Pressure
15 PSIG
9 PSIG
Safety Control (HP)
MON. 10:00 AM
Evap. Transducer
Evap. Pressure Transducer
or Probe Error
or Leaving Chilled Water
Thermistor (RS1)
MON. 10:00 AM
Motor Controller -
CM-2 or Solid State Starter or
Ext. Reset
Variable Speed Drive
MON. 10:00 AM
High Discharge
Discharge Temperature
220°F
219°F
Temperature
Thermistor (RT2)
MON. 10:00 AM
High Oil
Oil Temperature
180°F
179°F
Temperature
Thermistor (RT3)
MON. 10:00 AM
Power
Autostart
Microboard undervoltage
8.29VDC
7.84VDC
Failure
circuit on 5V unregulated
supply
MON. 10:00 AM
Power
Microboard undervoltage
8.29VDC
7.84VDC
Failure
circuit on 5V unregulated
supply
SHUTDOWN CAUSE
CONTROL CENTER DISPLAY