Refrigerant Level Setpoint
Displays the setpoint to which the refrigerant level is
being controlled.
Ramp Up Time Remaining
Displays the time remaining in the period in which the
Refrigerant Level Setpoint is being ramped to the Refrig-
erant Level Target Setpoint. This only displayed if the
Refrigerant Ramp is in effect and the value is non-zero.
PROGRAMMABLE
High Pressure Warning Threshold
Access Level Required:
SERVICE
This value allows the user to define the condenser pres
-
sure at which the chiller will initiate a warning.
Drop Leg (Enabled / Disabled)
Access Level Required:
SERVICE
When a Drop Leg Refrigerant Sensor has been installed
it must be enabled via this toggle before the system will
utilize the new, enhanced resolution input.
NAVIGATION
Home
Access Level Required:
VIEW
Causes an instant return to the Home Screen.
Purge
Access Level Required:
VIEW
Moves to the subscreen allowing programming of the
Purge System Setpoints.
Refrigerant Level Control
Access Level Required:
SERVICE
Moves to the sub-screen allowing programming of the
Refrigerant Level control setpoints.