background image

Service

Information

EBMPapst Variable Speed Fan  

Troubleshooting Guide 

 

 

File In/With:

    

Equipment  

Affected:

YVAA, YVFA, YVAM

New

SI0487

 

Product Technical Support

OVERVIEW

This Service Information Letter is to provide information on the troubleshooting of the EBMPapst Variable Speed 

Fan. The motors used with these fans have electronics built into the motor so standard motor troubleshooting pro-

cedures may not apply.

CAUTION: Do not attempt to megger the motor. The motor contains electronic components. Attempt-

ing to megger these motors will damage the motor electronic components.

PROCEDURES

1.  Identify the motor(s) that are not functioning.
2.  Verify that power is applied to the motors.

a.  It may be necessary to enable fan contactors through the chiller software depending on unit options (refer 

to appropriate service manual for fan wiring schematics).

  i.    Ensure Unit Switch is in OFF (0) position.
 ii.  Press SERVICE key. Type 9675 on keypad and press ENTER (Checkmark) key.
iii.  Use UP and DOWN arrow keys to scroll through service screens to the OUTPUT displays.
iv.    Use RIGHT or LEFT arrow keys to turn ON and OFF the condenser fan outputs and use UP or DOWN 

arrow keys to cycle through each condenser fan output. Turn ON “SYS1 COND FAN OUT 1” through 

“4” or “SYS2 COND FAN OUT 1” through “4” depending on which system you are testing.

NOTE: Make sure to stay in service menu to keep outputs on. Leaving the service screen 

will turn outputs off. Service menu will time out after a period of time. May be necessary 

to repeat steps if outputs turn off.

 

Work on this equipment should only be done by properly trained personnel who are qualified to work on this 

type of equipment. Failure to comply with this requirement could expose the worker, the equipment and the building 

and its inhabitants to the risk of injury or property damage.

 

The instructions on this service information letter are written assuming the individual who will perform this work 

is a fully trained HVAC & R journeyman or equivalent, certified in refrigerant handling and recovery techniques, and 

knowledgeable with regard to electrical lock out/tag out procedures. The individual performing this work should be 

aware of and comply with all Johnson Controls, national, state and local safety and environmental regulations while 

carrying out this work. Before attempting to work on any equipment, the individual should be thoroughly familiar 

with the equipment by reading and understanding the associated service literature applicable to the equipment. If 

you do not have this literature, you may obtain it by contacting a Johnson Controls Service Office.

 

Should there be any question concerning any aspect of the tasks outlined in this bulletin, please consult a 

Johnson Controls Service Office prior to attempting the work. Please be aware that this information may be time 

sensitive and that Johnson Controls reserves the right to revise this information at any time. Be certain you are 

working with the latest information.