Lifting weights
See
Figure 15
,
Figure 19
,
Figure 23
, and
Figure 27
for lifting location information. All published
weights in this manual are approximate values at the time of publication. Refer to the unit
nameplate or submittal documents for the actual unit shipping weight.
Note:
Weight can vary depending on unit configuration at the time of lifting.
Moving the chiller
Before moving the unit, ensure that the installation site is suitable for installing the unit and can
easily support the weight of the unit and all associated services.
Lifting using accessory lifting lugs
Units are provided with lifting holes in the base frame that accept the accessory lifting lug set
as shown in
Figure 14
. Insert the lugs (RH and LH) into the respective holes in the base frame.
Turn the lugs so that the spring loaded pin engages into the hole and the flanges on the lug lock
behind the hole. The lugs must be attached to the cables or chains using shackles or safety hooks.
See
Figure 14
for lug installation technique and
Figure 15
,
Figure 19
,
Figure 23
, and
Figure 27
for
installation locations.
Figure 14: YVAM chiller rigging using accessory lifting lugs
Callout
Component
Callout
Component
A
Lug
C
Flange
B
Lifting hole in base frame
D
Locking pin
YVAM Air-Cooled Centrifugal Liquid Chiller
18