Recommended clearances for all units
• For access to the unit control center, make sure that the unit is not higher when using spring
isolators.
• Minimum clearances are shown in
Figure 31
and are as follows:
- Side to wall: 6 ft (1.8 m)
- Rear to wall: 6 ft (1.8 m)
- Control panel end to wall: 4 ft (1.2 m)
- Top: No obstructions whatsoever
- Distance between adjacent units: 10 ft (3 m)
Figure 31: Unit clearance dimensions, ft (m)
• Ensure that no more than one wall around the chiller yard is higher than the chiller.
• Avoid locations near windows or structures where normal operating sounds might be
objectionable.
YVAM Air-Cooled Centrifugal Liquid Chiller
26