CAUTION
The evaporator liquid loop must be filled before conducting the following tests to prevent damage to
the heaters for the evaporator related components.
The following is a list of the devices that must be verified:
• Evaporator waterbox heaters WBH1 and WBH2
• Evaporator shell heaters EVH1 and EVH2
• Heat trace for VSD coolant HT1 and HT2
• VGD actuator heater mat
• MBC heater mat
• VSD internal heater
• OptiView Control Panel heater
• OptiView Control Panel cooler
• UPS panel heating
YVAM Air-Cooled Centrifugal Liquid Chiller
40