5567611-BIM-B-1218
Johnson Controls Ducted Systems
53
ZV-12 (12.5 Ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied drive
Standard 3 HP and drive
3200
736
0.44
774
0.79
816
1.12
861
1.41
910
1.68
960
1.92
1012
2.15
1065
2.36
1118
2.57
1171
2.77
3400
751
0.64
789
1.00
831
1.32
877
1.61
925
1.88
975
2.13
1027
2.35
1080
2.57
1133
2.77
1186
2.98
3600
768
0.87
806
1.22
848
1.55
894
1.84
942
2.11
992
2.35
1044
2.58
1097
2.79
1150
3.00
1203
3.20
3800
787
1.11
825
1.47
867
1.79
913
2.09
961
2.35
1011
2.60
1063
2.83
1116
3.04
1169
3.25
1222
3.45
4000
808
1.38
846
1.74
888
2.06
933
2.35
982
2.62
1032
2.86
1084
3.09
1137
3.31
1190
3.51
1242
3.71
4200
830
1.67
868
2.03
910
2.35
956
2.64
1004
2.91
1054
3.15
1106
3.38
1159
3.59
1212
3.80
1265
4.00
4400
854
1.98
892
2.33
934
2.66
980
2.95
1028
3.21
1078
3.46
1130
3.69
1183
3.90
1236
4.11
1289
4.31
4600
880
2.30
918
2.66
960
2.98
1005
3.28
1053
3.54
1104
3.79
1156
4.01
1209
4.23
1262
4.43
1314
4.64
4800
907
2.65
945
3.01
987
3.33
1032
3.62
1081
3.89
1131
4.13
1183
4.36
1236
4.58
1289
4.78
1341
4.98
5000
935
3.01
973
3.37
1015
3.69
1061
3.99
1109
4.25
1160
4.50
1212
4.73
1264
4.94
1317
5.15
1370
5.35
5200
965
3.40
1003
3.75
1045
4.08
1091
4.37
1139
4.64
1190
4.88
1242
5.11
1294
5.32
1347
5.53
1400
5.73
5400
996
3.80
1034
4.16
1076
4.48
1122
4.77
1170
5.04
1221
5.28
1273
5.51
1326
5.72
-
-
-
-
5600
1029
4.22
1067
4.57
1109
4.90
1155
5.19
1203
5.46
1253
5.70
-
-
-
-
-
-
-
-
5800
1063
4.65
1101
5.01
1143
5.33
1188
5.62
-
-
-
-
-
-
-
-
-
-
-
-
6000
1098
5.10
1136
5.46
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
6200
1134
5.57
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
High static 5 HP and drive