5567611-BIM-B-1218
8
Johnson Controls Ducted Systems
Table 2: ZV-06 through -12 unit limitations
Size
(tons)
Model
Unit voltage
Unit limitations
Applied voltage
Outdoor DB temp
Minimum
Maximum
Maximum (°F)
-06
(6.5)
ZV
208/230-3-60
187
252
125
460-3-60
432
504
125
-07
(7.5)
ZV
208/230-3-60
187
252
125
460-3-60
432
504
125
-08
(8.5)
ZV
208/230-3-60
187
252
125
460-3-60
432
504
125
-10
(10.0)
ZV
208/230-3-60
187
252
125
460-3-60
432
504
125
-12
(12.5)
ZV
208/230-3-60
187
252
125
460-3-60
432
504
125