Table 42: ZV-12 charging table - system 1
Table 43: ZV-12 charging table - system 2
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction
temp.
Discharge
pressure
Liquid temp. Delta T Db
Entering evap
Db
Leaving evap
Db
300 CFM/ton
80/62
75
127
52
268
75
31
80
49
85
131
52
311
85
29
80
51
95
134
53
359
95
28
80
52
300 CFM/ton
80/67
75
139
58
272
76
26
80
55
85
142
58
315
85
25
80
55
95
146
58
363
95
24
80
56
300 CFM/ton
80/72
75
150
66
278
76
20
80
60
85
155
64
322
86
19
80
61
95
159
64
370
96
18
80
62
300 CFM/ton
75/62
75
127
52
267
75
26
75
49
85
131
52
311
85
24
75
51
95
135
52
361
95
23
75
52
400 CFM/ton
80/62
75
134
54
270
76
27
80
53
85
138
54
314
86
25
80
55
95
143
54
362
96
24
80
56
400 CFM/ton
80/67
75
145
61
275
76
22
80
58
85
149
59
318
86
21
80
59
95
153
59
365
96
20
80
60
400 CFM/ton
80/72
75
155
69
279
76
16
80
64
85
160
67
322
86
16
80
64
95
165
66
370
96
15
80
65
400 CFM/ton
75/62
75
133
54
271
76
22
75
53
85
136
54
314
86
21
75
54
95
140
54
363
96
20
75
55
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction
temp.
Discharge
pressure
Liquid temp. Delta T Db
Entering evap
Db
Leaving evap
Db
300 CFM/ton
80/62
75
124
55
265
75
31
80
49
85
127
55
306
85
29
80
51
95
131
56
352
95
28
80
52
300 CFM/ton
80/67
75
135
61
268
76
26
80
55
85
139
61
311
85
25
80
55
95
142
61
357
95
24
80
56
300 CFM/ton
80/72
75
146
68
273
76
20
80
60
85
150
67
316
86
19
80
61
95
155
67
363
96
18
80
62
300 CFM/ton
75/62
75
124
54
264
75
26
75
49
85
128
55
306
85
24
75
51
95
131
56
354
95
23
75
52
400 CFM/ton
80/62
75
132
58
266
75
27
80
53
85
135
58
308
85
25
80
55
95
141
59
356
95
24
80
56
400 CFM/ton
80/67
75
141
65
271
76
22
80
58
85
146
64
313
85
21
80
59
95
150
64
358
95
20
80
60
400 CFM/ton
80/72
75
150
71
275
75
16
80
64
85
155
71
317
85
16
80
64
95
160
70
363
95
15
80
65
400 CFM/ton
75/62
75
131
58
268
75
22
75
53
85
134
57
309
85
21
75
54
95
138
57
356
95
20
75
55