WIRING INFORMATION
MODEL 41342 TEMPERATURE SENSOR
Resistance vs. Temperature for 1000
Ω
nominal probe
Temperature Coefficient = 0.00375
Ω
/
Ω
/°C
1226.445
140
1205.659
130
1184.837
120
1163.978
110
1143.081
100
1122.148
90
1101.177
80
1080.169
70
1059.124
60
1038.042
50
1016.922
40
995.766
30
974.572
20
953.340
10
932.069
0
910.759
-10
889.407
-20
868.013
-30
846.576
-40
825.093
-50
Resistance °F
Ω
60
1226.445
50
1189.005
40
1151.445
30
1113.764
20
1075.963
10
1038.042
0
1000.000
-10
961.837
-20
923.550
-30
885.132
-40
846.576
-50
807.873
Transfer function calculated from manufacturer's data:
C° = (1.1279x10
-5
*
R
2
) + (2.3985x10
-1
*
R) - 251.1326
F° = (2.0302x10
-5
*
R
2
) + (4.3174x10
-1
*
R) - 420.0387
NOTE:
The terminal marked "EARTH GND"
should be connected to properly grounded tower,
or grounding conductor, as close to the sensor as
possible. Failure to do so may result in damage
due to static discharge.
°C Resistance
Ω