Electro-Pneumatic Positioner

YT-1000R

13. CAUTION AND HANDLING

c

Do not apply large vibration or impact to the positioner.

It causes trouble. 

The positioner must be handled very carefully during transportation and operation.

d

If the positioner is used under temperature outside of the specification, the sealing

materials deteriorate quickly and also the positioner may not operate normally. 

e

Do not remove the terminal cover at a dangerous position during power conduction.  

f

Be sure that the terminal cover and body cover are put on during the operation. 

g

If you leave the positioner at the operation site for a long time without using it, put the

cover on it so that the rain water does not enter the positioner.  
If the atmosphere is of high temperature or high humidity, take measures to avoid
condensation inside.  The condensation control measures must be taken thoroughly for
export shipment.

14. TROUBLE SHOOTING

Replace Cam Shaft 

Cam shaft is worn out

Tighten connection

Loose connection of actuator and 
poisitioner

Readjust Seat adjuster

Wrong setting of Seat Adjuster

Hysteresis is not good

Replace regulator

Supply pressure is unstable

Readjustment of Zero, Span 
Adjustment

Wrong Zero, Span adjustment

Readjust setting of feedback lever

Wrong setting of feedback lever

Linearity is not good

Correct position of tube

Wrong connection of OUT1 and 
OUT2 tube

Actuator is operated by 
On/Off only

Clean or replace fixed orifice

Clogged fixed orifice

Insert orifice

Too low of actuator volume

Insert stabilizer spring

Off-positioned stabilizer spring

Hunting is occured

Clean nozzle or repalce Motor 
Unit

Clogged nozzle 

Output pressure is operated 
by A/M Switch only

Clean or replace fixed orifice 

Clogged fixed orifice

Replace Motor Unit

Wrong contact or search of Flapper

Tighten or replace A/M switch

Leakage of A/M switch

OUT1 pressure raised
And stay, does not
Come down

Correct setting and tighten

Loose or wrong setting of Feedback
Lever

Replace Motor Unit

Clogged Nozzle

Replace Motor Unit

Short or open circuit of terminal 
Motor

Connect wiring (+) and (-)

Wrong wiring for (+) and (-)

Tighten set screw of Terminal

Loose connection

Input supply air

Too low or none supply air

Not operated with Input
Signal applied

What to do

Cause

Condition

ЧП

 

Мельникова

 http://kran.net.ua E-mail: sergey_mel@farlep.net

Summary of Contents for YT-1000R

Page 1: ...Electro Pneumatic Positioner YT 1000 Series Instruction Manual YT 1000R Rotary Type http kran net ua E mail sergey_mel farlep net...

Page 2: ...ation 8 1 Example of attaching to actuator p3 8 2 Connection with feedback shaft p3 8 3 Cam attaching procedure p4 8 4 Attaching procedure of opening degree p4 indication plate 8 Block Diagram p3 7 Pr...

Page 3: ...e Low air consumption Easy to protect from hunting effect by using output orifice in small size of actuator Designed as block build structure for maintenance and repair 3 SPECIFICATIONS Double Acting...

Page 4: ...exerted by Torque Motor reduces Nozzle Back Pressure with increase in gap between between Flapper and Nozzle Then Spool moves upward and the Seat opens simultaneously Air pressure of OUT1 pipe is disc...

Page 5: ...ctuator Attach to the position at which the positioner feedback shaft and the rotary actuator main shaft are almost concentric range in which the spring pin of feedback shaft edge enters the hole of f...

Page 6: ...ce line and the bearing contact point of span adjusting arm unit to the matching position 3 Do not apply the supply pressure when attaching the cam as otherwise it is very dangerous 4 When the positio...

Page 7: ...ose its connection 10 ELECTRICAL WIRING c Connect the and output terminals from the regulator with the and input terminals respectively of the positioner Junction box d For Explosion Proof both pressu...

Page 8: ...e Stroke starting signal 4mA then turn the Zero Adjuster clockwise or counterclockwise d In case of Spring Actuator check if it is set to standard pressure in Zero Point If not repeat Zero adjustment...

Page 9: ...pter 15 OPTION 12 MAINTENANCE AND CHECK c If the supply air is fouled the positioner may not operate normally Periodically check the compressed air cleaning system and make sure that clean air is alwa...

Page 10: ...Wrong setting of Seat Adjuster Hysteresis is not good Replace regulator Supply pressure is unstable Readjustment of Zero Span Adjustment Wrong Zero Span adjustment Readjust setting of feedback lever...

Page 11: ...ription in chapter 4 Ordering Symbols None Over 180 1 0 90 180 0 7 Below 90 Ordering No Output orifice diameter Volume of actuator e After pulling out the O ring from OUT1 and OUT2 port push proper or...

Page 12: ...Electro Pneumatic Positioner YT 1000R 16 DIMENSIONS 0 Rotary Positioner http kran net ua E mail sergey_mel farlep net...

Reviews: