background image

- 35 -

Parameter mode (PARAM)

Parameter types

There are four types in parameter of Dead Zone, KP, KI, KD.

These values are reflected as soon as they are changed, therefore the appropriate values

are found with checking valve's motion by real time.

Dead Zone (dEAdZONE)

This is the section of Error % that I control is not operated. If there are hunting or

oscillation continuously due to the friction between stem and packing, they are prevented

with this parameter.

KP

This is proportion constant value of correction that is correcting by Error %. If this value

is too big, there can be hunting though it finds position by input signal. If the value is

too small, accuracy gets worse.

KI

This is integral constant value adding or subtracting the correction that is correcting by

Error % on previous correction signal. If this value is too big, there can be oscillation. If

it is too small, the time to find the exact position gets longer.

KD

This

is

differential

constant

value

adding

previous

correction

signal

with

changing

correction signal by Error % change rate.

Adjustment of Parameter

Dead zone (dEAdZONE)

(1) Push <ENTER> at RUN mode for 6 seconds and AUTO CAL message is appeared.

(2) Push <DOWN> twice and PARAM mode is displayed.

(3) Push <ENTER> and dEAdZONE mode is displayed.

(4) Push <ENTER> again and *EAdZONE message is appeared.

(5) Adjsut dEAdZONE value by <UP> or <DOWN>. Adjusted value is applied right away

without additional operation, so users can easily check its adjustment by changing current

input signal to YT-2300. It means that optimum control value is found by adjusting values

during valve operation.

- 36 -

(6) Push <ENTER> to save the value. +EAdZONE message is on LCD.

(7) Push <ESC> three times to return to RUN mode.

(1) Push <ENTER>

(2) Push <DOWN> twice.

(3) Push <ENTER>.

for 6 seconds.

(4) Push <ENTER>.

(5) Push <ENTER>

(6) Push <ESC>.

after adjustment

by <UP>, <DOWN>.

(7) Push <ESC> twice.

RUN

Mode

KP

(1)-(3) Adjustment method and procedure is as same as dEAdZONE.

(4) Push <DOWN> at dEAdZONE mode and KP mode is displayed.

(5) Push <ENTER> and *KP message is on LCD.

(6) Adjust KP values with <UP> or <DOWN>. Adjusted value is applied right away

without additional operation, so users can easily check its adjustment by changing current

input signal to YT-2300. It means that optimum control value is found by adjusting values

during valve operation.

(7) Push <ENTER> to save the value. +KP message is on LCD.

(8) Push <ESC>.

(9) Push <ESC> twice to return to RUN mode.

(1) Push <ENTER>

(2) Push <DOWN> twice.

(3) Push <ENTER>.

for 6 seconds.

Summary of Contents for YT-2300 Series

Page 1: ...2300L installation 13 Example 13 Installing YT 2300L with bracket 14 YT 2300R installation 18 Example 18 Installing YT 2300R with bracket 19 Piping connection 22 Note 22 Conditions of supply pressure...

Page 2: ...oducts Our products are produced and inspected under the strict standards In order to use the products appropriately and efficiently we recommend that users read this manual carefully and fully unders...

Page 3: ...hunting is controlled to the optimum condition during operation 9 Hart communication makes to process various information of valve and positioner 10 Valve system is stable by outputting analog feedba...

Page 4: ...7 MPa Serial number The numbers given each product By tracking this number various information for the item can be collected YT 2300 Label 8 Ordering number YT 2300 series use the following ordering...

Page 5: ...r Quick Open EQ User Set 16 Point Vibration Effect 6G Humidity 5 95 RH at 40 Communication Option HART Communication Non DDL Feedback Signal Option 4 20mA DC 10 30V Material Aluminum Diecasting Weight...

Page 6: ...must be shut down In order entire system not to shut down the control valve must be separated from the system by bypass valve or other equipment No pressure remains in the actuator YT 2300L drawing Y...

Page 7: ...it is necessary to make proper bracket to attach on actuator yoke The most important things in making bracket are as follows 1 YT 2300L feedback lever should be level at 50 of valve stroke Refer to n...

Page 8: ...e stroke Connection of supply pressure pipe between actuator and air filter regulator 16 6 Insert connection bar attached on actuator clamp into the slot of YT 2300L feedback lever Ensure that inserti...

Page 9: ...feedback lever reaches to the lever stopper move attachment position of YT 2300L to the direction becoming more distant from yoke center Check whether or not lever stopper and feedback lever is conta...

Page 10: ...r using hexagon head bolts or wrench bolts Diameter of bracket bolt holes is 6mm Use spring washers or any other equipment so as the bolts not to be loosened by vibration or impact The direction of br...

Page 11: ...pring This is to fit the main shaft of YT 2300R and the center of actuator stem If they are not fitted product durability is getting worse due to too much force on the main shaft of YT 2300 22 Connect...

Page 12: ...pipe whose inner diameter is more than 6mm outer diameter 10mm 4 Do not connect the pipe too long It affects flow rate due to the friction inside the pipe Piping connection with actuator Single actin...

Page 13: ...nstall the cable near the equipment such as high capacity transformer or motor generating noise The following is terminal part of YT 2300 series Terminal plate of YT 2300 Terminal connection of curren...

Page 14: ...ground cable terminal to prevent it coming out A M switch Auto Manual switch There is A M switch on the bottom of YT 2300 If this switch is set as auto supply pressure is transmitted to actuator by t...

Page 15: ...gnal There are six types displayed in Run mode Run PV Valve stroke of Process Value Run SV Input signal of Set Value 0 100 Run SV mA Input signal of Set Value 4 20mA Run MV Motor controlled variable o...

Page 16: ...TO CAL The calibration of YT 2300 is simply performed by Auto calibration and there are 5 types of Auto calibration as AUTO1 AUTO2 AUTO3 BIAS V_0 AUTO1 calibration is useful for users in the field and...

Page 17: ...line on LCD indicates the value close to zero After valve is stopped Usually the number is between 2 to 2 If the number is over 5 execute this function again and reset V_0 value 1 Push DOWN at BIAS m...

Page 18: ...r 6 seconds and AUTO CAL message is appeared 2 Push DOWN twice and PARAM mode is displayed 3 Push ENTER and dEAdZONE mode is displayed 4 Push ENTER again and EAdZONE message is appeared 5 Adjsut dEAdZ...

Page 19: ...WN twice 3 Push ENTER for 6 seconds 4 Push DOWN twice 5 Push ENTER 6 Push ENTER after adjustment with UP DOWN 38 7 Push ESC 8 Push ESC twice RUN Mode Kd 1 3 Adjustment method and procedure is as same...

Page 20: ...to RUN mode 6 In order to change valve end point push DOWN at PV_ZERO mode and PV_END mode is started 7 Push ENTER at PV_END mode and PE mode is displayed At this mode it is available to change valve...

Page 21: ...42 Valve mode This mode is to adjust the various characteristics Action type ACT It is set Direct Action DA and Reverse Action RA Characteristics CHAR It is set Characteristics There are three types...

Page 22: ...d ACT RA or ACT DA is displayed 2 Push DOWN twice then USER SET mode is started 3 Push ENTER P0 SET mode is displayed and at this mode users can adjust the first point of characteristic in sixteen poi...

Page 23: ...ode 1 Push DOWN 2 Push ENTER 3 Push ENTER four times after adjustment with UP DOWN 4 Push ESC RUN Mode three times 46 Adjustment of Split Range SPLIT 1 Push ENTER at VALVE mode and ACT RA or ACT DA is...

Page 24: ...ause Measures A None None B The range of Pv Span Pv Zero is less than 500 Operating angle of feedback is too small Adjust operating angle of feedback lever to be bigger Refer P 13 and execute AUTO 1 c...

Page 25: ...Kyeonggi Do Korea TEL 0082 31 986 8545 FAX 0082 31 986 2683 E mail ytc ytc co kr Homepage http www ytc co kr http www positioner biz This information contained in this catalogue is subject to change w...

Reviews: