YT-3300/3301 series
6.3.5.6 Split Range Mode (SPLIT)
The valve can be operated by split range control – 4~12mA or 12~20mA.
6.3.5.7 Custom Zero Setting Mode (CST ZERO)
Custom Zero Setting Mode allows the user to set any specific point as zero position. For
example, the zero point can be set at input signal of 7mA.
6.3.5.8 Custom End Setting Mode (CST ENd)
Custom End Setting Mode allows the user to set any specific point as end position. For
example, the end point can be set at input signal of 11mA.
The difference between zero
and end point must be greater or equal to 4mA.
6.3.5.9 Interpolation Mode (ITP OFF / ON)
Positioner can control the valve accurately if the feedback lever angle range is within
designed range. For some instance, the angle exceeds the suggested range angle.
Positioner can reduce the error through interpolation.
⇨