background image

  Yudian (H.K.) Automation Technology Co. Ltd. 

                                                                                       

Website: 

http://www.yudian.us

   

http://www.yudian.com.hk

  

                                                                                                                                                                      Email: 

sales@yudian.com.hk

  

Tel: +852-2770 8785   Fax: +852-2770 8796 

 

I. Model Order Code 

The type of AI-208 is made up of 4 parts

 

AI-208

 

A

 

G

 

L2

 

Part 1 (Series) 

Part 2 (Size) 

Part 3 (Oupt) 

Part 4 (AUX) 

 

1.  (Part 1) Model Series 

AI-208, standard temperature controller , 0.3%FS±1

 accuracy. 

Multiple thermocouples and RTDs are selectable 

Suitable for 0~999

 application. Maximum support two alarms contact output 

Universal supply power (100~240VAC)   

 

2.  (Part 2) Front panel dimension   

Panel Size 

Front Panel 

width×height

 

Cut Out 

width×height

 

Depth Behind Mounting Surface 

A1 96×96mm 

92×92mm 

70mm 

B1 160×80mm 

152×76mm 

70mm 

D1 72×72mm 

68×68mm 

78.5mm 

E1 48×96mm 

vertical 

45×92mm 

70mm 

F1 96×48mm 

horizontal 

92×45mm 

70mm 

A 96×96mm 

92×92mm 

100mm 

B 160×80mm 

152×76mm 

100mm 

D 72×72mm 

68×68mm 

95mm 

D2 48×48mm 

45×45mm 

95mm 

E 48×96mm 

45×92mm 

100mm 

F 96×48mm 

92×45mm 

100mm 

Summary of Contents for AI-208

Page 1: ...omation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 208 V7 8 Ope...

Page 2: ...tiple thermocouples and RTDs are selectable Suitable for 0 999 application Maximum support two alarms contact output Universal supply power 100 240VAC 2 Part 2 Front panel dimension Panel Size Front P...

Page 3: ...city 2A 250VAC normal open support AU1 and AU2 alarm output G SSR voltage output module 30mA 5VDC D1 sized controller is fixed to SSR output G and no module option provided i e AI 208 D1 G AI 208 D1 G...

Page 4: ...ously jumps out from parameter setting to the default status The instrument will also jumps out auomatically from the parameter table if no key is pressed in 30 seconds Setting Loc 808 and then press...

Page 5: ...ction because of the fluctuation of PV AHY 2 by default 0 200 AOP Alarm output assignment HdA x100 LdA LoA x10 HIA x1 0 0 0 1 AU1 1 AU1 1 AU1 2 AU2 2 AU2 2 AU2 5 AU1 AU1 6 AU2 AU1 7 AU1 8 AU2 9 AU1 AU...

Page 6: ...s 0 200 InP Input specification Thermocouples RTD 0 K 4 E 5 J 7 N 21 Pt100 0 21 dPt Resolution 0 or 0 0 selectable 0 0 is valid for 0 99 9 display Scb Input shift Scb is used to make input shift to co...

Page 7: ...ed is for upright panel dimension A A1 E E1 For panel dimension B B1 F F1 please rotate the diagram clockwise by 90 degree Panel dimension D 72 x 72mm Panel dimension D1 D2 48 x 48mm Remarks 1 Thermoc...