V. PARAMETER AND SETTING 

 

Field parameter table (Press        and hold for 2 seconds to access) 

Code Name 

Description 

Setting 

Range

HIA 

High limit alarm 

Alarm on when PV (Process Value) >HIA; 

alarm off when PV<HIA-AHY 

0

999

 

LoA 

Lower Limit 

alarm 

Alarm on when PV (Process Value) < LoA;   

alarm off when PV > LoA+AHY 

0

999

 

HdA 

Deviation high 

alarm 

Alarm on when PV-SV>HdA;   
alarm off when PV-SV<HdA-AHY 

0

999

 

Loc Parameter 

Lock 

Loc=0~1: Allowed to modify parameters HIA, LoA, HdA and SV.

Loc=2~3: Allowed to modify parameters HIA, LoA, HdA. But cannot 

change SV. 

Loc=4~255: NOT allowed to modify any parameters and SV. 

Loc=808, Set to 808 and press          , allowed modify all parameters. 

0

255 

 

AHY 

Hysteresis 

Avoid frequent alarm on-off action because of the fluctuation of PV, 

usually sets to AHY=2 

0~200 

AOP 

Alarm output 

assignment 

Alarm

Output to   

HdA 

(x100)

LoA 

(x10) 

HIA 

(x1) 

None 

0 0  0 

AU1 

1 1  1 

AU2 

2 2  2 

eg: AOP=201 means HdA have alarm action from AU2, LoA, no alarm 

action , HIA alarm action output from AU1. 

0~444 

CrL Control 

mode 

z

  onF : On-off control, When PV=SV, Output stop. When 

PV<SV-CHY, start output. 

z

 

AI : AI PID control, high precision and no-overshoot,   

 

Proportion band 

Proportion band in PID with unit 

  

1~999 

Time of Integral 

Time of Integral in PID. No integral effect when I=0 

0~999 Sec 

Time of 

Derivative 

Time of Derivative in PID. No derivative effect when d=0 

0~999 Sec 

Ctl Control 

period 

Small value can improve control accuracy.   

For SSR output, generally 0.5 to 3 seconds. 

For Relay output, generally 15 to 40 seconds, because small value will 

cause the frequent On-Off of mechanical switch and shorten its service 

life.  Ctl is recommended to be 1/4 – 1/10 of derivative time. When 

control under on-off control, Ctl use as restart delay time after off, for 

protect compressor application.   

0.5-300 SEC 

CHY 

Control 

Hysteresis 

CHY is used for ON-OFF Control.   
PV > SV, Output turns OFF; 
PV<SV-CHY, Output turns ON. 

0~200 

InP 

Input 

specification 

Sn 

Input spec. 

Sn 

Input spec.   

0 K 

1-3 

Spare 

4 E 

5 J 

6 Spare 

7 N 

8-20 Spare 

21  Pt100 

 

0

21 

Scb Input 

Shift 

Scb is used to make input shift to compensate the error produced by 
sensor or input signal. 
PV after compensation= PV before compen Scb. 

-99

+99

 

Summary of Contents for AI-208

Page 1: ...ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 208 V7 6 User Manual ...

Page 2: ...e Suit for 0 999 application Maximum support two alarms contact output Universal voltage input 100 240VAC ISO9001 certification and CE certified achieving word class level of quality anti interference ability and safety 2 Part 2 Front panel dimension Size Front Panel width height Cut Out width height Depth Behind Mounting Surface A 96 96mm 92 92mm 100mm B 160 80mm 76 152mm 100mm D 72 72mm 68 68mm ...

Page 3: ...upport AL1 and AL2 alarm output G SSR voltage output module 30mA 5VDC II TECHNICAL SPECIFICATION 1 Input type Thermocouple K E J N Resistance temperature Detector Pt100 2 Instrument Input range K E J N 0 999 Pt100 0 800 3 Measurement accuracy 0 3 FS 1 4 Temperature display resolution 1 5 Control mode On off control mode AI artificial intelligence control including fuzzy logic PID control and advan...

Page 4: ...igence control and auto tuning When AI artificial intelligence control method is chosen CrL AI the PID parameters can be obtained by running auto tuning In basal display status press for 2 seconds the At parameter will appear Press to change the value of At from oFF to on then press to active the auto tuning process During auto tuning the instrument executes on off control After 2 3 times of on of...

Page 5: ...L Control mode z onF On off control When PV SV Output stop When PV SV CHY start output z AI AI PID control high precision and no overshoot P Proportion band Proportion band in PID with unit 1 999 I Time of Integral Time of Integral in PID No integral effect when I 0 0 999 Sec d Time of Derivative Time of Derivative in PID No derivative effect when d 0 0 999 Sec Ctl Control period Small value can i...

Page 6: ...d FIL s can be set to 0 or 1 to shorten the response time 0 40 Fru Selection of power frequency and temperature scale 50C 50Hz 50F 50Hz 60C 60Hz 60F 60Hz SPH Upper limit of SV Maximum value that SV allowed to be When SPH 400 the SV range will 0 400 0 999 VI INSTRUMENT INSTALLATION AND WIRING Wiring graph for instruments with dimension A B E or F Note The graph suits for upright instruments with di...

Page 7: ...Wiring graph for D2 dimension 48X48mm instruments 1 2 3 4 5 6 7 9 10 8 COM N O 100 240VAC AU1 AUX AU2 COM COM N O N C N O N O Main Output OUTP Alarm Output ...

Reviews: