AI-508 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER 

Operation Instruction Version 7.0 

 

 

 

 

 

 

 

GENERAL 

AI-508, an economical and easy operated model of Yudian artificial intelligent industry controller, is specially designed for use in the industries of plastic 
machinery, food machinery, packaging machinery, baking machinery and environmental testing equipment.    It features: 

● 

Application of artificial intelligence control algorithm with auto tuning function, avoiding the overshoot problem of standard PID algorithm and 
achieving precise control.   

● 

Multiple thermocouples and RTDs are selectable.  Integrated non-linear graduation tables, digital calibration and auto zero technology, and 
achieving accurate and stable measurement. 

● 

Advanced modular structure, conveniently providing various outputs options, and making quick delivery and easy maintenance. 

● 

universal 100

240VAC power supply. 

● 

ISO9001, ISO14001 and CE certified, achieving world class level of quality, anti-interference ability and safety. 

 

MODEL CODE SYMBOL 

The type of AI-508T is made up of 5 parts, for example: 

          AI-508      A        G        L2        L2   

                                       

       

     

       

       

 

  shows the basal function of instrument 

 

AI-508    economical artificial intelligence temperature controller 

  shows the front panel dimension :

   

 

Front panel 96

×

96mm(width

×

height), cut out 92

×

92mm, depth behind mounting surface 100mm 

 

Front panel 72

×

72mm(width

×

height), cut out 68

×

68mm, depth behind mounting surface 95mm 

 

D2  Front panel 48

×

48mm(width

×

height), cut out 45

×

45mm, depth behind mounting surface 95mm 

 

Front panel 48

×

96mm(width

×

height), cut out 45

×

92mm, depth behind mounting surface 100mm 

 

Front panel 96

×

48mm(width

×

height), cut out 92

×

45mm, depth behind mounting surface 100mm 

    shows the module types of main output.    Selectable modules are as follows:

 

 

L1  Relay output module (Capacity: 2A/250VAC, normally open terminal can absorb electrical spark) 

 

L4  Relay output module (Capacity: 2A/250VAC, small volume, normally open terminal can absorb electrical spark) 

 

SSR voltage output module (30mA/12VDC)   

 

W1  TRIAC no contact normally open discrete output module, suitable for AC contactors up to 80A, and has low interference and long life. 

 

K1    Single phase thyristor zero crossing trigger output module. (can trigger three-phase of TRIAC, a pair of inversely parallel connected SCRs or 

TRIAC power module of current 5-500A) 
 

K3    Three phases Thyristor zero crossing trigger output module.    (can trigger three-phase of TRIAC, a pair of inversely parallel connected SCRs 

or TRIAC power module of current 5-500A) 

④ 

shows the module type of alarm output.    Selectable modules are as follows: 

N (or none)    no module installed   
L1 

Relay contact output module (Capacity: 2A/250VAC, normal open terminal can absorb spark, support AL1 alarm output) 

L2 

Relay contact output module (Capacity: 1A/250VAC, small volume, support AL1 alarm output) 

L5 

Output module of dual normal open relay output (Capacity: 2A/250VAC, support AL1 and AL2 alarm output) 

  shows the module type of Auxiliary output (AUX). Selectable modules are as follows: 

N (or none)    no module installed 

 

L1  Relay contact output module (Capacity: 2A/250VAC, normal open terminal can absorb spark, support AU1 alarm output) 

 

L2  Relay contact output module (Capacity: 1A/250VAC, small volume, support AU1 alarm output) 

 

L5  Output module of dual normal open relay outputs(Capacity: 2A/250VAC, support AU1 and AU2 alarm output) 

Note1:  

For instrument of dimension D2, because of its limited volume, when L1 or L5 module is installed in the ALM socket, L1 can’t be installed in the 
OUPT socket, but L4, which is smaller,    can be installed instead. 

Note2:  

K3 can’t be installed in instruments with dimension D or D2.    There is no ALM socket in D2 instruments.    L5 module can’t be installed in the 
ALM socket of instrument with dimension D. 

 