background image

9

Figure 8. Unit horizontally Suspended

Threaded 

Rod

Lag
Bolt

Nuts (x2)

Washer 

and 

Lockwasher

Nuts (x2)

ELECTRICAL CONNECTIONS

 WARNING:

ELECTRICAL ShOCK, FIRE OR EXPLOSION 
hAZARD

Failure to follow safety warnings exactly could 
result in serious injury or property damage.
Improper servicing could result in dangerous 
operation, serious injury, death or property 
damage.

•  Before servicing, disconnect all electrical power 

to the electric furnace.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly

.

•  Verify proper operation after servicing.

Electrical power wiring must be made in accordance with 
all applicable local codes and ordinances, and with the 
current revision of the National Electric Code (ANSI/NFPA 
70). For Canadian installations, the electrical connections 
and grounding shall comply with the current Canadian 
Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

 Verify the voltage, frequency, and phase of the supply 

source match the specifications on the unit rating plate.

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 
See the unit wiring label or Table 4 (page 15) for proper 
high and low voltage wiring.

 Verify factory wiring is in accordance with the unit 

wiring diagrams (Figures 11-14, pages 16-19). Verify no 
connections came loose during shipping or installation.

Line Voltage

• 

An electrical disconnect must be located within 
sight of and readily accessible to the unit

. This 

switch shall be capable of electrically de-energizing 
the outdoor unit control voltage. See unit data label for 
proper incoming field wiring. Any other wiring methods 
must be acceptable to authority having jurisdiction.

•  It is recommended that the line voltage to the unit be 

supplied from a dedicated branch circuit containing the 
correct fuse or circuit breaker for the unit.

•  The  installer  should  become  familiar  with  the  wiring 

diagram/schematic before making any electrical 
connections to the unit. See the unit wiring label or 
Figures 11-14 (pages 16-19).

The unit may also be installed in a horizontal application 
with the unit suspended from the ceiling. If suspending the 
electric furnace from the ceiling, assemble a support frame 
using slotted iron channel and full threaded rod. Fasten 
the frame together with nuts, washers, and lockwashers. 
Secure the support frame to the rafters with lag bolts. 
The electric furnace can also be suspended using steel 
straps around each end of the unit. The straps should be 
attached to the electric furnace with sheet metal screws 
and to the rafters with bolts.

To attach the supply air duct to the electric furnace, bend 
the perforated flanges (Figure 5, page 8) upward 90° with 
a pair of wide duct pliers. Position the duct against the 
electric furnace, align the openings, and secure together 
with sheet metal screws. Make sure the screws penetrate 
the sheet metal casing and flange. Tape or seal all seams 
if required by local code.

To attach the return air duct to the electric furnace, position 
the duct against the electric furnace, align the openings, 
and secure together with sheet metal screws. Make sure 
the screws penetrate the sheet metal casing and electric 
furnace. Tape or seal all seams if required by local code.

A/C or h/P Coil Installation

Approved air conditioning and heat pump system 
components are listed on the unit nameplate. To install 
the indoor coil:
1. Remove door cover plate, door and coil close-off plate 

(with insulation). Discard door cover plate.

2. Upflow Applications: Slide the coil into the track located 

in the bottom of the unit.

  Downflow Applications: The downflow adaptor must be 

used (see Table 1). Install the downflow adaptor and coil 
as directed in the instructions supplied with the kit.

3. Reinstall the door and coil close-off plate (with insulation). 

NOTE:

 In downflow applications the door is rotated 180° 

so that the refrigerant and condensate lines remain on 
the left side.

4. Install the refrigerant and condensate lines as directed 

in the instructions supplied with the outdoor unit.  

NOTE: 

The drain pan MUST be drained with field 

supplied tubing and looped to form a trap. Both drain 

tubes must have a minimum diameter of 3/4” and be 
trapped separately. 

IMPORTANT:

 Failure to install a trap 

may result in condensation overflowing the drain pan, 
resulting in substantial water damage to surrounding 
area.

Summary of Contents for 000K-B-10

Page 1: ...cial notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Please read all instructions care...

Page 2: ...Supply Circuits 10 Control Board 10 Twinning 10 Thermostat Low Voltage Connections 10 Grounding 10 Startup Adjustments 11 Before You Start the Unit 11 Air Circulation Check 11 Running the Blower Conti...

Page 3: ...ctric Code ANSI NFPA 70 For Canadian installations the electrical connectionsandgroundingshallcomplywiththecurrent Canadian Electrical Code CSA C22 1 and or local codes Installationofequipmentmayrequi...

Page 4: ...rant tubing This unit should be located with consideration of minimizing the length of the supply and return ducts Refer to the rating plate or Table 3 page 15 for proper circulating airflow data Figu...

Page 5: ...essure shown on the furnace rating plate The supply air must be delivered to the heated space by duct s secured to the furnace casing running full length and without interruption Circulating Air Suppl...

Page 6: ...r best sound performance be sure to install all the needed gaskets and grommets around penetrations into the electric furnace such as for electrical wiring Air Filters B5BV series electric furnaces ar...

Page 7: ...th sheet metal screws Make sure the screws penetrate the sheet metal casing and flanges Tape or seal all seams if required by local code NOTE If an upflow pedestal mounting stand is fabricated in the...

Page 8: ...nnector and cut out the marked area of the supply air duct NOTE Toallowsomeclearanceforinstallingtheplenum connector cut the opening 1 4 larger the actual cutout drawn 6 Install the duct connector bac...

Page 9: ...lso be installed in a horizontal application with the unit suspended from the ceiling If suspending the electricfurnacefromtheceiling assembleasupportframe using slotted iron channel and full threaded...

Page 10: ...ce controls the timing sequence of the elements The board is equipped with a 3 second blower ON delay and a 15 second blower OFF delay in heating and a 40 second blower OFF delay in cooling Twinning E...

Page 11: ...temperature above room temperature and observe that the blower energizes Checktheairbeingdischargedattheregister is warmer than room temperature 2 Allow the unit to run for several minutes and then se...

Page 12: ...s recommended that the filter be cleaned or replacedmonthly Newlybuiltorrecentlyrenovatedhomes mayrequiremorefrequentchanginguntiltheconstruction dust has minimized Filter sizes shown in Table 2 are a...

Page 13: ...B 19 3 4 18 1 4 49 3 8 C 22 1 2 21 56 3 4 3 4 3 4 13 1 7 8 K O 11 8 K O typ 11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W...

Page 14: ...Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Blower Wheel Blower Housing Motor Control Board Control Board Filter Door Upper Door Assembly Lower Door Assembly Figure 10 B5BV Ser...

Page 15: ...1576 1783 NOTES 1 Airflow is shown in cfm 5 2 All airflows are measured without filter and with dry coil For filter velocity of 300 ft min subtract 08 external static pressure For wet coil subtract 1...

Page 16: ...peed tap connection may not be as shown See the Installation Instructions 2 Disconnect all power before servicing 3 Transformer may have a dual voltage primary tap Match the tap position with the supp...

Page 17: ...GREY BLUE ORANGE POWER PLUG LIMIT RED RED RED RED BLACK BLACK RED BLACK RELAY RELAY TERMINAL BLOCK for select models only CIRCUIT BREAKER Circuit breaker models only BLUE W2 W1 O Y Y2 G R C X13 MOTOR...

Page 18: ...d 4 If the Internal wiring is replaced use only 105 C copper wire of the same gauge W2 W1 O Y Y2 G R C 4 SPD MOTOR 1 2 3 5 6 4 TRANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE L2 COM 2 L2 L2 COM L1 VS...

Page 19: ...ANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE BLOWER MOTOR PLUG C L G N N NEUTRAL G GROUND L LINE C COMMON L2 L2 L2 COM L1 L1 XFMR X13 COOL X13 HEAT 24 VAC RED COM GREY Y1 C L G N WHITE X13 COM RED B...

Page 20: ...h B5 Electric Furnace G R C E O Y Thermostat NOTE Jumper W1 W2 together for shorter staging time W2 W1 O Y G R C W2 W1 O Y G R C NOTE Jumper W1 W2 together for shorter staging time Air Handler W2 O W2...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...at been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct YES NO VENTING SYSTEM Is there adequate fresh air supply for ventilation YES NO Vent free from restrict...

Reviews: