background image

11

STARTUP & ADjUSTMENTS

Before You Start the Unit

Prior to start-up, complete the following inspections:

  Verify the unit is level and properly located with adequate 

clearances for servicing the unit. See Figure 1 (page 4) 
for clearance requirements.

 Check condensate drain line(s) for proper drainage (if 

applicable). See step 4 on page 9.

 Verify the surrounding area and top of the unit is free 

from obstructions and debris.

 Check all duct connections. Make sure the duct work 

is adequately sealed to prevent air leakage.

 Check all coil connections for leaks (if applicable).

 Verify that the line voltage power leads are securely 

connected and the unit is properly grounded. Make sure 
all doors are installed before restoring power to the unit

  Verify the thermostat is wired correctly. Make sure all 

low voltage wires are securely connected to the correct 
leads of the low voltage terminal strip.

 Verify the power supply branch circuit overcurrent 

protection is sized properly.

 Verify filter is properly and securely installed.

Air Circulation Check

Running the Blower Continuously
Set the thermostat’s system mode to 

OFF

 and the 

thermostat’s fan mode to 

ON

. The blower motor should 

run continuously. Check for air delivery at the register(s). 
Make sure that there are no obstructions at the registers 
or in the ducts.

NOTE:

 If blower is turning opposite of arrow direction, shut 

off main power to the unit and switch any two field wires 
at the disconnect. 

DO NOT 

alter unit wiring.

System Cooling
1. Set the thermostat’s system mode to 

COOL

 and fan 

mode to 

AUTO

. Lower the thermostat’s temperature 

mode below room temperature and observe that the 
blower energizes. Check the air being discharged at 
the register is cooler than room temperature. Verify 
unit refrigerant pressures are in order. Blower should 
be turning in direction indicated by arrow.

 NOTE:

 DO NOT alter unit wiring. Listen for any unusual 

noises. Locate the source and correct as needed.

2. Allow the unit to run for several minutes and then set 

the thermostat’s temperature above room temperature. 
Verify the blower cycles off with the thermostat.

System Heating
1. Set the thermostat’s system mode to 

hEAT

 and the fan 

mode to 

AUTO

. Increase the thermostat’s temperature 

above room temperature and observe that the blower 
energizes. Check the air being discharged at the register 
is warmer than room temperature.

2. Allow the unit to run for several minutes and then set 

the thermostat’s temperature below room temperature. 
Verify the blower cycles off with the thermostat.

Turning the Blower Off
Set thermostat’s fan mode to 

AUTO

, the blower will shut 

down immediately.

Blower Configurations

Determining Nominal System Capacity
To select the appropriate airflow for the electric furnace, 
the nominal system capacity must be known. The nominal 
system capacity is always the nominal capacity of the 
outdoor unit. However, in some situations the nominal 
system capacity may not be the same as the capacity 
rating of the electric furnace. Always refer to the capacity 
rating of the outdoor unit to determine the nominal system 
capacity.

Proper Blower Speed for Multi-Speed Units
The blower speed is preset at the factory for operation at 
the same speed for heating and cooling. Use the jumping 
terminal on the blower motor and connect it to the desired 
speed with both the red and black wires connected to the 
jumping terminal.

NOTES:

• 

The control board is programmed with a 40 second 
off delay in the cooling mode for optimum system 
performance and efficiency.

• 

When using a 20 kw electric heat kit in a downflow 
installation, the blower must be set for high speed for 
both heating and cooling.

For optimum system performance and comfort, it may be 
necessary to change the factory set speed. Refer to Table 
3 (page 15) for airflow data. To change the blower speed:

1. Disconnect all electrical power to the unit and remove 

the upper door.

2. Remove the black and red wires from the blower motor 

jumping terminal. Discard the blower motor jumping 
terminal.

3. Connect the heating speed wire (red) and the cooling 

speed wire (black) to the desired blower speed marked 
on the terminal block of the blower motor.

To change motor speed for standard 4-speed motors:

•  Terminal 2 = High speed
•  Terminal 3 = Medium High speed
•  Terminal 4 = Medium Low speed
•  Terminal 5 = Low speed

C Cabinet units are equipped with 5 selectable blower 
speeds. To change motor speed for standard 5-speed 
motors:

•  Terminal 1 = High speed
•  Terminal 2 = Medium Low speed
•  Terminal 3 = Medium speed
•  Terminal 4 = Medium High speed
•  Terminal 5 = High speed

4. Replace the upper door and secure it to the unit.
5. Restore power to the unit.

Summary of Contents for B5BV Series

Page 1: ...cial notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Please read all instructions care...

Page 2: ...Supply Circuits 10 Control Board 10 Twinning 10 Thermostat Low Voltage Connections 10 Grounding 10 Startup Adjustments 11 Before You Start the Unit 11 Air Circulation Check 11 Running the Blower Conti...

Page 3: ...ctric Code ANSI NFPA 70 For Canadian installations the electrical connectionsandgroundingshallcomplywiththecurrent Canadian Electrical Code CSA C22 1 and or local codes Installationofequipmentmayrequi...

Page 4: ...rant tubing This unit should be located with consideration of minimizing the length of the supply and return ducts Refer to the rating plate or Table 3 page 15 for proper circulating airflow data Figu...

Page 5: ...essure shown on the furnace rating plate The supply air must be delivered to the heated space by duct s secured to the furnace casing running full length and without interruption Circulating Air Suppl...

Page 6: ...r best sound performance be sure to install all the needed gaskets and grommets around penetrations into the electric furnace such as for electrical wiring Air Filters B5BV series electric furnaces ar...

Page 7: ...th sheet metal screws Make sure the screws penetrate the sheet metal casing and flanges Tape or seal all seams if required by local code NOTE If an upflow pedestal mounting stand is fabricated in the...

Page 8: ...nnector and cut out the marked area of the supply air duct NOTE Toallowsomeclearanceforinstallingtheplenum connector cut the opening 1 4 larger the actual cutout drawn 6 Install the duct connector bac...

Page 9: ...lso be installed in a horizontal application with the unit suspended from the ceiling If suspending the electricfurnacefromtheceiling assembleasupportframe using slotted iron channel and full threaded...

Page 10: ...ce controls the timing sequence of the elements The board is equipped with a 3 second blower ON delay and a 15 second blower OFF delay in heating and a 40 second blower OFF delay in cooling Twinning E...

Page 11: ...temperature above room temperature and observe that the blower energizes Checktheairbeingdischargedattheregister is warmer than room temperature 2 Allow the unit to run for several minutes and then se...

Page 12: ...s recommended that the filter be cleaned or replacedmonthly Newlybuiltorrecentlyrenovatedhomes mayrequiremorefrequentchanginguntiltheconstruction dust has minimized Filter sizes shown in Table 2 are a...

Page 13: ...B 19 3 4 18 1 4 49 3 8 C 22 1 2 21 56 3 4 3 4 3 4 13 1 7 8 K O 11 8 K O typ 11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W...

Page 14: ...Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Blower Wheel Blower Housing Motor Control Board Control Board Filter Door Upper Door Assembly Lower Door Assembly Figure 10 B5BV Ser...

Page 15: ...1576 1783 NOTES 1 Airflow is shown in cfm 5 2 All airflows are measured without filter and with dry coil For filter velocity of 300 ft min subtract 08 external static pressure For wet coil subtract 1...

Page 16: ...peed tap connection may not be as shown See the Installation Instructions 2 Disconnect all power before servicing 3 Transformer may have a dual voltage primary tap Match the tap position with the supp...

Page 17: ...GREY BLUE ORANGE POWER PLUG LIMIT RED RED RED RED BLACK BLACK RED BLACK RELAY RELAY TERMINAL BLOCK for select models only CIRCUIT BREAKER Circuit breaker models only BLUE W2 W1 O Y Y2 G R C X13 MOTOR...

Page 18: ...d 4 If the Internal wiring is replaced use only 105 C copper wire of the same gauge W2 W1 O Y Y2 G R C 4 SPD MOTOR 1 2 3 5 6 4 TRANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE L2 COM 2 L2 L2 COM L1 VS...

Page 19: ...ANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE BLOWER MOTOR PLUG C L G N N NEUTRAL G GROUND L LINE C COMMON L2 L2 L2 COM L1 L1 XFMR X13 COOL X13 HEAT 24 VAC RED COM GREY Y1 C L G N WHITE X13 COM RED B...

Page 20: ...h B5 Electric Furnace G R C E O Y Thermostat NOTE Jumper W1 W2 together for shorter staging time W2 W1 O Y G R C W2 W1 O Y G R C NOTE Jumper W1 W2 together for shorter staging time Air Handler W2 O W2...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...at been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct YES NO VENTING SYSTEM Is there adequate fresh air supply for ventilation YES NO Vent free from restrict...

Reviews: