background image

7

ELECTRIC FURNACE INSTALLATION

These Installation procedures are suggested for typical 
electric furnace installations. Since all installations are 
different from each other, the sequence of these steps may 
differ from the actual installation. 

Only qualified hVAC 

technicians should install this furnace

.

The B5BV series electric furnace is shipped ready for 
vertical upflow installation and is approved for attic, 
basement, alcove/closet or crawlspace installation with 
zero clearance to combustibles. See Figure 1 (page 4) 
for required installation clearances. 

This appliance is 

only for indoor use.

•  Remove the shipping crate and User’s Manual from the 

equipment.

•  The unit must be leveled at installation and attached to 

a properly installed duct system.

•  The  surface  that  the  electric  furnace  is  mounted  on 

must provide sound physical support of the unit.

•  The electric furnace must be installed so that all electrical 

components are protected from water.

•  If a louvered door is installed across the front of this 

unit, the appliance must be mounted flush or behind 
front edge of finished wall.

Upflow Installations

All electric furnaces are factory shipped, ready for upflow 
installation. All return air must enter from the bottom of the 
unit when installed in the upflow configuration. A typical 
upflow unit is shown in Figure 3.

Position the electric furnace on top of the return air duct 
and secure together with sheet metal screws. The screws 
must penetrate the sheet metal cabinet and duct. Tape or 
seal all seams if required by local code.

To attach the supply air duct to the electric furnace, bend 
the perforated flanges (Figure 5, page 8) upward 90° with 
a pair of wide duct pliers. Position the duct on top of the 
electric furnace and secure together with sheet metal 
screws. Make sure the screws penetrate the sheet metal 
casing and flanges. Tape or seal all seams if required by 
local code. 

NOTE:

 If an upflow pedestal mounting stand is fabricated 

in the field, the stand must be constructed strong 
enough to support the unit with all accessories installed 
(approximately 130 lbs. for B-cabinet models and 200 lbs. 
for C-cabinet models). The construction of the pedestal 
stand must also allow for at least 235 in

2

 free opening (300 

in

2

 for C-cabinet models) in the application. Field fabricated 

upflow pedestal mounting stands must be constructed of 
noncombustible materials. Position the electric furnace 
on top of the mounting stand and secure together with 
sheet metal screws. The screws must penetrate the sheet 
metal cabinet and duct. Tape or seal all seams if required 
by local code.

Downflow Installations

B5BV electric furnaces can be converted to downflow 
operation by flipping an upflow unit 180°. A typical 
installation of the unit in a downflow application is shown 
in Figure 3.

NOTE:

 Downflow installations require the use of a plenum 

connector (or its equivalent) if the supply air ducts pass 
through the floor of the structure. This factory supplied 
accessory must be installed in the floor cavity and attached 
to the supply air duct before the downflow unit is installed. 
Available plenum connectors for all B5BV electric furnaces 
are listed in Table 1. All return air in downflow applications 
must enter through the top of the unit.

Figure 3. Installation Configurations

Return

Air

Return

Air

UPFLOW

DOWNFLOW

Return

Air

HORIZONTAL RIGHT

Return

Air

HORIZONTAL LEFT

Table 1. Optional Accessory Kits

Description

Cabinet Size

B

C

Downflow Plenum Connector, 6.25”

913840 914969

Downflow Plenum Connector, 8.25”

913841 914970

Downflow Plenum Connector, 10.25”

913842 914971

Upflow Pedestal Mounting Stand

913872 913873

Downflow Coil Adaptor

919321

919322

*919323

* Use when installing B width coil in C width cabinet

Summary of Contents for B5BV Series

Page 1: ...cial notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Please read all instructions care...

Page 2: ...Supply Circuits 10 Control Board 10 Twinning 10 Thermostat Low Voltage Connections 10 Grounding 10 Startup Adjustments 11 Before You Start the Unit 11 Air Circulation Check 11 Running the Blower Conti...

Page 3: ...ctric Code ANSI NFPA 70 For Canadian installations the electrical connectionsandgroundingshallcomplywiththecurrent Canadian Electrical Code CSA C22 1 and or local codes Installationofequipmentmayrequi...

Page 4: ...rant tubing This unit should be located with consideration of minimizing the length of the supply and return ducts Refer to the rating plate or Table 3 page 15 for proper circulating airflow data Figu...

Page 5: ...essure shown on the furnace rating plate The supply air must be delivered to the heated space by duct s secured to the furnace casing running full length and without interruption Circulating Air Suppl...

Page 6: ...r best sound performance be sure to install all the needed gaskets and grommets around penetrations into the electric furnace such as for electrical wiring Air Filters B5BV series electric furnaces ar...

Page 7: ...th sheet metal screws Make sure the screws penetrate the sheet metal casing and flanges Tape or seal all seams if required by local code NOTE If an upflow pedestal mounting stand is fabricated in the...

Page 8: ...nnector and cut out the marked area of the supply air duct NOTE Toallowsomeclearanceforinstallingtheplenum connector cut the opening 1 4 larger the actual cutout drawn 6 Install the duct connector bac...

Page 9: ...lso be installed in a horizontal application with the unit suspended from the ceiling If suspending the electricfurnacefromtheceiling assembleasupportframe using slotted iron channel and full threaded...

Page 10: ...ce controls the timing sequence of the elements The board is equipped with a 3 second blower ON delay and a 15 second blower OFF delay in heating and a 40 second blower OFF delay in cooling Twinning E...

Page 11: ...temperature above room temperature and observe that the blower energizes Checktheairbeingdischargedattheregister is warmer than room temperature 2 Allow the unit to run for several minutes and then se...

Page 12: ...s recommended that the filter be cleaned or replacedmonthly Newlybuiltorrecentlyrenovatedhomes mayrequiremorefrequentchanginguntiltheconstruction dust has minimized Filter sizes shown in Table 2 are a...

Page 13: ...B 19 3 4 18 1 4 49 3 8 C 22 1 2 21 56 3 4 3 4 3 4 13 1 7 8 K O 11 8 K O typ 11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W...

Page 14: ...Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Blower Wheel Blower Housing Motor Control Board Control Board Filter Door Upper Door Assembly Lower Door Assembly Figure 10 B5BV Ser...

Page 15: ...1576 1783 NOTES 1 Airflow is shown in cfm 5 2 All airflows are measured without filter and with dry coil For filter velocity of 300 ft min subtract 08 external static pressure For wet coil subtract 1...

Page 16: ...peed tap connection may not be as shown See the Installation Instructions 2 Disconnect all power before servicing 3 Transformer may have a dual voltage primary tap Match the tap position with the supp...

Page 17: ...GREY BLUE ORANGE POWER PLUG LIMIT RED RED RED RED BLACK BLACK RED BLACK RELAY RELAY TERMINAL BLOCK for select models only CIRCUIT BREAKER Circuit breaker models only BLUE W2 W1 O Y Y2 G R C X13 MOTOR...

Page 18: ...d 4 If the Internal wiring is replaced use only 105 C copper wire of the same gauge W2 W1 O Y Y2 G R C 4 SPD MOTOR 1 2 3 5 6 4 TRANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE L2 COM 2 L2 L2 COM L1 VS...

Page 19: ...ANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE BLOWER MOTOR PLUG C L G N N NEUTRAL G GROUND L LINE C COMMON L2 L2 L2 COM L1 L1 XFMR X13 COOL X13 HEAT 24 VAC RED COM GREY Y1 C L G N WHITE X13 COM RED B...

Page 20: ...h B5 Electric Furnace G R C E O Y Thermostat NOTE Jumper W1 W2 together for shorter staging time W2 W1 O Y G R C W2 W1 O Y G R C NOTE Jumper W1 W2 together for shorter staging time Air Handler W2 O W2...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...at been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct YES NO VENTING SYSTEM Is there adequate fresh air supply for ventilation YES NO Vent free from restrict...

Reviews: