YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, Pennsylvania • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
Page 36
NJEX EUR ver. 08-2021
Section 6: Programming for Proportional-to-Time Operation
Setting Operator Input Parameters,
Continued
To set the alarm level points,
figure 68
, press and
release the
Select
key. The Odorant Inlet Low value
will begin to flash when chosen. Nominal low pressure
in the Odorant Storage Tank is
2.07 Bar
. Use the
Up
Arrow
key to increase the value and the
Down Arrow
key to decrease the value. When a new value has
been chosen, press the
Enter
key to store the new
Odorant Inlet Low setting into memory. The entered
value will stop flashing when it has been loaded into
memory and the Odorant Inlet High value will begin to
flash. Nominal high pressure in the Odorant Storage
Tank is
2.41 Bar
. Use the
Up Arrow
key to increase
the value and the
Down Arrow
key to decrease the
value. When a new value has been chosen, press the
Enter
key to store the new Odorant Inlet High setting
into memory. Press the
Down Arrow
key to advance
to the next menu.
Alarm to Relay Delay
Is a programmable time that can be entered to allow
for a period of time to occur between the initial issu-
ance of an alarm and the actual remote reporting of
the alarm via the alarm relay output.
1. 0 = No Relay Contact Delay
2. 1 - 240 = Number of Minutes Delay
3. > 240 = Disabled, No Alarm Relay Contact will oc-
cur
To set the alarm delay time
,
figure 69
, press and
release the
Select
key. The Alarm to Delay value
will begin to flash when chosen. Use the
Up Arrow
key to increase the value and the
Down Arrow
key
to decrease the value. When a new value has been
chosen, press the
Enter
key to store the value.
Alarm to Call Out Delay
Is a programmable time that can be entered to allow
for a period of time to occur between the initial issu-
ance of an alarm and the actual automatic call out
function via a modem or Modbus communication port.
1. 0 = No Alarm Call Out Delay
2. 1 - 240 = Number of Minutes Delay
3. > 240 = Disabled, No Alarm Call Out will occur
Or
Figure 68
Figure 69
pmp bat vmtr sig tnk
Odorant Inlet (psi)
25.0=Low 40.0=High
pmp bat vmtr sig tnk
Odorant Inlet (bar)
1.70=Low 2.80=High
pmp bat vmtr sig tnk
Alarm to Relay Delay
0 minutes
pmp bat vmtr sig tnk
Alarm to Callout Dly
0 minutes