Page 50
NJEX EUR ver. 08-2021
Section 8: Working with the N-300 System Displays
To View Real-Time Displays,
Continued
Expansion Tank
This display illustrates the expansion tank pressure,
figure 129
.
Odorant Inlet
Displays the pressure of the bulk odorant storage
tank via the pressure transmitter located at the fill rate
control valve,
figure 130
.
Battery Voltage
The battery voltage is shown in this display,
figures
131
.
•
Battery Alarm,
a low battery is when the voltage is
less then 11.5 VDC.
Flow Input
This display,
figure 132,
illustrates the flow rate as a
percentage of the maximum gas flow. The following
represent the alarms that are associated with this area
of the N-300G controller.
Flow Input Alarms
•
Loss of Signal,
figure 133,
the flow signal is less
than .5 VDC, for the analog input only.
•
Over Flow,
figure 134,
the flow input has exceeded
125% of the maximum gas flow.
Flow Input Indicators, non-alarm
•
Low Flow,
figure 135,
the flow input has fallen be-
low the low flow shut off set point
Programming for Proportional-to-Flow page 26
•
Over Flow
,
figure 136,
the flow input has exceeded
110% of the maximum gas flow, but is still less than
125% of maximum gas flow.
•
No Flow,
figure 137,
is presently indicated by the
flow signal.
•
Low Flo Shtoff,
figure 138,
the flow signal indicates
a flow rate less than programmed for odorization.
Or
Or
pmp bat vmtr sig tnk
Battery 14.3 VDC
pmp bat vmtr sig tnk
Odorant Inlet
35.3 psig
pmp bat vmtr sig tnk
Odorant Inlet
2.434 bar
pmp bat vmtr sig tnk
Expansion Tank
25.2 psig
pmp bat vmtr sig tnk
Expansion Tank
1.739 bar
Figure 129
Figure 130
pmp bat vmtr SIG tnk
Flow Input 0.0%
Pulse (PPM)
Loss of Signal
pmp bat vmtr sig tnk
Battery 14.3 VDC
Low Battery
pmp bat vmtr sig tnk
Flow Input 63.1%
Linear
pmp bat vmtr sig tnk
Flow Input 0.0%
Pulse (PPM)
pmp bat vmtr SIG tnk
Flow Input 125.1%
Pulse (PPM)
OverFlow >125%
pmp bat vmtr sig tnk
PropFlow 0.06
*Stop *Dsp *Set
Low Flow Shtoff
pmp bat vmtr sig tnk
Flow Input 110.1%
Pulse (PPM)
OverFlow >110%
pmp bat vmtr sig tnk
Flow Input 0.0%
Pulse (PPM)
No Flow
pmp bat vmtr sig tnk
Flow Input 2.0%
Pulse (PPM)
Low Flo Shtoff
Figure 131
Figure 131
Figure 132
Figure 133
Figure 134
Figure 135
Figure 136
Figure 137
Figure 138