Section 9: Setting & Testing Alarms
Testing Alarm Out Status
Continued
To Simulate the pump alarm status,
figures 160,
press and release the
Select
key. The
pmp Alarm
in-
dicator in the upper left area of the N-300G display will
flash when it is selected. Use the
Down Arrow
or
Up
Arrow
keys to simulate which type of pump alarm to
activate. This will be shown by the solid block appear-
ing next to
Over Pump
,
Under Pump
, or
Pump Fail-
ure
text at the top of the N-300G display, and the
PMP
indicator will be displayed in UPPER CASE letters, and
will flash on and off. Press the
Enter
key to return to
the simulation selection screen. The display will stop
flashing. Press the
Down Arrow
key to advance to the
next simulation option.
To Simulate the battery alarm status
,
figures 161,
press and release the
Select
key. The
bat
alarm
indicator in the upper left center area of the N-300G
display will flash when it is selected . Use the
Down
Arrow
or
Up Arrow
keys to simulate a
Low Battery
alarm. This will be shown by the solid block appear-
ing next to
Low Battery
text at the top of the N-300G
display, and the
BAT
indicator will now be displayed
in UPPER CASE letters, and will flash on and off.
Press the
Enter
key to return to the simulation selec-
tion screen. The display will stop flashing. Press the
Down Arrow
key to advance to the next simulation
option.
To Simulate the verometer alarm status,
figures 162,
press and release the
Select
key. The
vmtr
alarm in-
dicator in the upper center area of the N-300G display
will flash when it is selected. Use the
Down Arrow
or
Up Arrow
keys to simulate which type of Verom-
eter alarm to simulate. This will be shown by the solid
block appearing next to
Odor Inlet-Cabl
,
Odor Inlet
Lo
,
Odor Inlet Hi
,
XTank-Cable
,
XTank Low
,
XTank
High
,
Flvalve-Fail
,
Leakage
,
Slow Fill
,
No Fill
, or
Vmtr-Cable
, text at the top of the N-300G display, and
the
VMTR
indicator will now be displayed in UPPER
CASE letters, and will flash on and off. Additionally,
at this position two Verometer Indicators,
Overfill
and
Fillrate
, that are non-alarms may be simulated in the
same manner. They will be indicated at the same loca-
tion on the N-300G display, but will not have the solid
block appearing next to them, and the
vmtr
indicator
will again be in the lower case, but will continue to flash
off and on.
pmp bat vmtr sig tnk
Pump Alarm
Simulate
Figure 160
pmp bat vmtr sig tnk
Battery Alarm
Simulate
pmp BAT vmtr sig tnk
Battery Alarm
Simulate
Low Battery
pmp bat vmtr sig tnk
Verometer Alarm
Simulate
pmp bat VMTR sig tnk
Alarm Output Status
*Set *Test *Esc
XTank High
pmp bat VMTR sig tnk
Alarm Output Status
*Set *Test *Esc
Vmtr-Cable
pmp bat VMTR sig tnk
Alarm Output Status
*Set *Test *Esc
No Fill
pmp bat VMTR sig tnk
Alarm Output Status
*Set *Test *Esc
Slow Fill
pmp bat VMTR sig tnk
Alarm Output Status
*Set *Test *Esc
Leakage
pmp bat VMTR sig tnk
Alarm Output Status
*Set *Test *Esc
Flvalv-Fail
pmp bat VMTR sig tnk
Verometer Alarm
Simulate
Odor Inlet-Cable
pmp bat VMTR sig tnk
Verometer Alarm
Simulate
Odor Inlet Low
Odor Inlet Hi
pmp bat VMTR sig tnk
Verometer Alarm
Simulate
pmp bat VMTR sig tnk
Verometer Alarm
Simulate
XTank-Cable
pmp bat VMTR sig tnk
Verometer Alarm
Simulate
XTank-Low
PMP bat vmtr sig tnk
Pump Alarm
Simulate
Over Pump
PMP bat vmtr sig tnk
Pump Alarm
Simulate
Under Pump
PMP bat vmtr sig tnk
Pump Alarm
Simulate
Pump Failure
Figure 160
Figure 160
Figure 160
Figure 161
Figure 161
Figure 162
Figure 162
Figure 162
Figure 162
Figure 162